RKHH2E-(P)AAV33
ROTEX Domestic Hot Water Heat Pump
2018.8
Installation manual
29
8.1.3.13 Defrosting
Defrosting is enabled:
•
Automatically, when the temperature of the
evaporator is below the temperature established in
parameter d17 (only if P4 has a value other than 0);
In any case, the compressor must have been left
switched on for a period either longer than or equal
to d18 minutes between two defrosting procedures.
Otherwise the request to enable the defrosting
procedure will not be accepted.
If P4 = 1, d2 represents the temperature of the
evaporator. The defrosting procedure terminates
when the temperature exceeds the temperatures
represented by d2.
If P4 = 0 or P4 = 2, parameter d2 is not taken into
consideration.
If during the defrosting procedure the evaporator or
thermistor is above the threshold set by parameters
d2 and P4 = 1, the request to enable the defrosting
procedure is not accepted.
•
The parameter d3 establishes the maximum
duration of the stage.
•
When defrosting mode is on, the heating
element will commence operation
If the “Anti-Legionella” or the “Overboost”
functions are in progress, the defrosting
procedure cannot be enabled.
8.1.3.14 Day and real time settings
•
Make sure that the keyboard is not locked
(paragraph 0) and that no other advanced
procedures are in progress;
•
Press and release the
key: the first available
code will appear on the display;
•
Press and release either the
or the
key
until “
rtc
” appears;
The day is displayed as 1...7 (number 1 corresponding
to Monday).
To change the day of the week:
•
Press and release the
key: the display will
show “
dd
” followed by two numbers representing
the day;
•
Press and release either the
or the
key
within the next 15 seconds.
To change the time:
•
Press and release the
key while changing the
day of the month: the display will show “
hh
”
followed by two numbers representing the time (in
24 hr. format);
•
Press and release either the
or the
key
within the next 15 seconds.
To change the minutes:
•
Press and release the
key while changing the
time: the display will show “
nn
” followed by two
numbers representing the minutes;
•
Press and release either the
or the
key
within the next 15 seconds;
•
Press and release the
key or do not carry out
any operations for 15 seconds;
To exit the procedure:
•
Press and release the
key until the
temperature established by parameter P5 appears
on the display or do not carry out any operations
for 60 seconds.
Alternatively:
•
Press and release the
key.
Prior to performing operations within timeslots,
you should have carried out the settings
relating to the day and the real time.