8.1.3.11 Alarms 

 

N

OTE

 

In case of “

UtL

” alarm (fault of the fan), in 

addition to the display visualization, the 
equipment emits an acoustic signal that 
can be switched off pressing any key on 
the user interface. The alarm is never 
cancelled unless the equipment is 
switched off or put in stand-by. 

The heat pump working mode is automatically 

disabled and the one with electric 
resistance is activated in order to ensure 
the continuity of the warm water supply.  

 

 

PLEASE

 

NOTE! 

In case of “UtL” alarm, you must contact the 

technical assistance. 

 

AL 

Minimum temperature alarm 

Solution:  

-

 Check the temperature associated with the 

alarm; 

-

 Parameters  

-

 displayed: A0, A1, A2 and A11. 

Main consequences:  

-

 The equipment will continue working regularly

 

AH 

Maximum temperature alarm 

Solutions:  

-

 Check the temperature associated with the 

alarm; 

-

 Parameters displayed: A3, A4, A5 and A11. 

Main consequences:  

-

 The equipment will continue working regularly.

 

id 

Digital input alarm 

Solutions:  

-

 Check the causes that initiated the input 

activation (possible short circuit in signal 
cables)  

-

 See parameters: i0; i1 and i2; 

Main consequences:  

-

 Compressor will be switched off; 

-

 Defrosting will not be activated. 

iSd 

Blocked equipment alarm 

Solutions:  

-

 Check the causes that initiated the digital 

input activation  

-

 See parameters: i0; i1; 18 and i9 

-

 Switch off the equipment and restart it, or 

disconnect the equipment from the mains 
power supply.  

Main consequences:  

-

 Compressor will be switched off; 

-

 Defrosting will be never activated. 

FiL 

Ventilation filter check alarm 

Solutions: 

-

 Check how clean the filter is (to switch off the 

alarm message, press any key on the 
display) 

UtL 

Probable fan fault 

Solutions:  

-

 See parameters SP10 and C14 

-

 Check the fan conditions 

Main consequences:  

-

 Compressor and fan are switched off; 

-

 Water heating occurs, using only the electric 

resistance. 

 

 

When the error causing alarm has been 

resolved, normal operation of the 
equipment is restored.

 

 

8.1.3.12 Error messages 

Pr1 

Error in thermistor in upper part of the boiler  

Solutions:  

 

-

 Check whether the type of thermistor is in 

conformity with parameter P0 settings; 

-

 Check whether the thermistor is intact; 

-

 Check the equipment-thermistor 

connection; 

-

 Check the temperature of the upper part of 

the boiler. 

Main consequences:  

-

 The equipment stops working.

 

Pr2 

Error in thermistor in lower part of the boiler 

Solutions: 

-

 Identical to solution for 

error in thermistor in 

upper part of the boiler

 (see above), but 

applied to the lower part. 

Main consequences: 

-

 The equipment stops working.

 

Pr3 

Error in evaporator thermistor 

Solutions: 

-

 Identical to solution for error in thermistor in 

upper part of the boiler (see above), but 
applied to the evaporator thermistor. 

-

 The equipment stops working. 

 

 

When the error causing alarm has been 

resolved, the normal operation of the 
equipment is restored. 

Содержание RKHH2E200AAV33

Страница 1: ...Installation Manual Installation manual Domestic Hot Water Heat Pump Monobloc type RKHH2E200AAV33 RKHH2E260AAV33 RKHH2E260PAAV33 Domestic Hot Water Heat Pump Monobloc type English...

Страница 2: ......

Страница 3: ...RKHH2E P AAV33 ROTEX Domestic Hot Water Heat Pump 2018 8 Installation manual 3...

Страница 4: ...ing limits 16 5 5 Fundamental safety rules 16 5 6 Information on coolant used 16 6 Installation and connections 17 6 1 Preparation of the installation site 17 6 2 Ventilation connection 17 6 2 1 Parti...

Страница 5: ...ead the service manual For more information see the installer and user reference guide 1 2 For the user If you are not sure how to operate the unit contact yourinstaller This appliance can be used by...

Страница 6: ...o NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are preferably carried out under dry weather conditions to avoid...

Страница 7: ...ssor breakdown do NOT charge more than the specified amount of refrigerant When the refrigerant system needs to be opened refrigerant must be treated according to the applicable legislation WARNING Ma...

Страница 8: ...a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure t...

Страница 9: ...to the unit Installation manual Instruction manual designed for a certain unit or application explaining how to install configure and maintain it Operation manual Instruction manual designed for a ce...

Страница 10: ...able to instructions figures drawings or descriptions without prejudice to errors of any kind The Supplier shall not be held responsible for damages attributable to misuse improper use or as a consequ...

Страница 11: ...power etc Version Configuration description RKHH2E200AAV33 RKHH2E260AAV33 Air source heat pump for the production of domestic hot water RKHH2E260PAAV33 Air source heat pump for the production of domes...

Страница 12: ...t of a structural nature WARNING The equipment can be transported horizontally only during the last km following the instructions in the section Positions permitted for transporting and handling above...

Страница 13: ...160 mm 13 Hermetically sealed rotary compressor 14 Replaceable magnesium anode 15 1 5 kW 230 W Electric heating element 16 Condenser pump discharge line 17 Condenser return 18 Replaceable magnesium a...

Страница 14: ...element power kW 1 5 1 5 1 5 Maximum current in HP A 2 4 2 4 2 4 Required overload protections A 16A T fuse 16A automatic switch characteristic C to be expected during installation on power supply sys...

Страница 15: ...Mg anode 26x250 mm 1 x Mg anode 26x250 mm 1 x Mg anode 26x400 mm Insulation 50 mm high density polyurethane foam Defrosting Active with Hot Gas valve Dimensions mm H1714xD600xDmax650 H2000xD600xDmax6...

Страница 16: ...ate functional monitoring system with alarm functions in order to avoid such damage being caused Moreover it is necessary to arrange for a back up service in case of failure 5 4 Operating limits The a...

Страница 17: ...r connection to the condense drain Be available and ready with adequate discharge pipes in case of damage caused to the boiler or actuation of the safety valve or breakage of pipes connections Have co...

Страница 18: ...ickness Sound mufflers can be mounted when deemed necessary Fit the pipes the holes in the wall and the connections to the heat pump with vibration damping systems WARNING The simultaneous operation o...

Страница 19: ...ersions A B C D E F G mm mm mm mm mm mm mm 650 1714 600 160 1101 795 H I J K L M N mm mm mm mm mm mm mm 70 150 380 195 O P mm mm 337 5 10 6 4 Water supply connections Connect the cold water inlet and...

Страница 20: ...rol device of the check valve a safety valve and a device to interrupt the water load Fig 8a N B The drain pipe connected to the equipment for protection against overpressure must be installed sloping...

Страница 21: ...n via siphon with water shut off valve 6 5 Solar power system integration Fig 10 is an example of solar power system integration Cold water intake pipe Solar power system pump and accessories Solar co...

Страница 22: ...e brown yellow and the water temperature measured by lower thermistor is higher than SP8 the heat pump stops and water is heated by the solar panels The heat pump restarts when the contact stops and t...

Страница 23: ...fication plate The commissioning procedure should be completed by following these steps Fill the boiler by connecting the water inlet tap and check for any leaks from gaskets and connections Tighten t...

Страница 24: ...Stand by mode In the stand by mode the instrument can automatically switch on at certain time slots and independently enables the anti Legionella and defrosting functions When the equipment is switch...

Страница 25: ...een finished the function is automatically disabled and the equipment is automatically restored to the Automatic or Economy mode depending on which one was previously set by the user ANTI LEGIONELLA o...

Страница 26: ...keyboard follow this procedure Make sure that no other advanced procedures are in progress Press and hold the and the keys until Loc will appear on the display for 1 second If the keyboard is locked i...

Страница 27: ...slot operation in order to avoid malfunctions caused by users 8 1 3 7 Display of the operating status Make sure that the keyboard is not locked paragraph 0 and that no other advanced procedures are in...

Страница 28: ...ivation See parameters i0 i1 18 and i9 Switch off the equipment and restart it or disconnect the equipment from the mains power supply Main consequences Compressor will be switched off Defrosting will...

Страница 29: ...ngs Make sure that the keyboard is not locked paragraph 0 and that no other advanced procedures are in progress Press and release the key the first available code will appear on the display Press and...

Страница 30: ...ures are in progress Press and hold the and keys for 4 seconds PA password will appear on the screen Press and release the key Press and release either the or the key within the next 15 seconds to set...

Страница 31: ...the compressor and consequently lead to breakdown of the equipment At every Start up the fan is activated for an amount of time set by parameter C12 1 minute After this amount of time the system meas...

Страница 32: ...Lower thermistor calibration CA2 C F 25 0 25 0 0 0 Evaporator thermistor calibration CA3 C F 25 0 25 0 0 0 Thermistor type P0 0 1 1 0 PTC 1 NTC 2 PT1000 Decimal point P1 0 1 1 1 Display decimal point...

Страница 33: ...r stopped Evaporator temperature to conclude defrosting procedure only if P4 1 d2 C F 50 0 50 0 3 0 Maximum duration of defrosting procedure d3 min 0 99 8 Automatic defrosting start threshold evaporat...

Страница 34: ...for digital input alarm counter reset i9 min 1 999 240 Buzzer enabling u9 0 1 1 0 Buzzer disabled 1 Buzzer enabled Switching on time for Monday Hd1 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for...

Страница 35: ...RKHH2E P AAV33 ROTEX Domestic Hot Water Heat Pump 2018 8 Installation manual 35 Parameter description Code U M Min Max Default Notes 1 ODD 2 EVEN RESERVED E9 0 2 0...

Страница 36: ...necessary to Disconnect the device from the mains power supply Remove any air ducts see paragraph 0 Remove the upper cover by undoing the appropriate locking screws Fig 18 Manually reset the tripped...

Страница 37: ...ctrochemical potential in comparison to the material that coates the inside of the boiler It therefore attracts the negative charges that are formed during the heating of the water and would cause the...

Страница 38: ...regulations WARNING This equipment contains greenhouse fluorinated gas included in the Kyoto protocol The maintenance and disposal operations must only be carried out by qualified personnel INFORMATIO...

Страница 39: ...mperature settings of the water heater C 55 Sound power level Lwa indoors in dB dB 53 The water heater is able to work only during off peak hours NO Any specific precautions that shall be taken when t...

Страница 40: ......

Страница 41: ......

Страница 42: ...r im Ausland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani...

Отзывы: