background image

RKHH2E-(P)AAV33 
ROTEX Domestic Hot Water Heat Pump 
2018.8 

 

Installation manual  

27

 

 

 

 

N.B. 

Before proceeding with the timeslot settings, 

set day and real time as described in 
paragraph 0. 

 

To start the procedure: 

 

Make sure that the keyboard is not blocked and 
that no other advanced procedures are in 
progress; 

 

Press and release the 

 

key: “SP1” will appear 

on the display. 

 

To set the timeslots: 

 

Press and release either the 

 or the 

 key 

within the next 15 seconds to select “

HOn1

” (first 

switching on 

time) and/or “

HOf1

” (first switching 

off time); select “

HOn2

” and “

HOF2

” for the 

second switching on/off time; 

 

Press and release the 

 key; 

 

Press and release either the 

 or the 

 key 

and within the next 15 seconds to set the timeslot 

 

Press and release the 

 key or do not perform 

any other operations for 15 seconds. 

 

To associate a time slot to a certain day of the week: 

 

After the previous procedure has been carried out, 

press either the 

 or the 

 key and realease 

it within 15 seconds 

in order to select “

Hd1

” 

(switch on time for day 1, i.e. Monday) and/or 

Hd2...7

” (switching on time for days 2-7, 

Tuesday-Sunday); 

 

Press and release the 

 key; 

 

Press and release either the 

 or the 

 key 

within 15 seconds to select “1” (the first switch 
on/off time) or “2” (the second switch on/off time); 

 

Press and release the 

 key or do not perform 

any other operations for 15 seconds. 

 

To exit the procedure before its completion: 

 

Do not perform any operations for 15 seconds 

(any changes will be saved) or press the 

 key 

shortly. 

 

 

Carefully evaluate enabling of time slot operation 

in order to avoid malfunctions caused by 
users. 

8.1.3.7 Display of the operating status

 

 

Make sure that the keyboard is not locked 
(paragraph 0) and that no other advanced 
procedures are in progress; 

Press and release the 

 key: Auto/ECO/Obst/Anti will 

be displayed for 3 seconds depending on the current 
active operative status.

 

8.1.3.8 Silencing of the alarm sound 

To silence the alarm, follow this procedure: 

 

Press any key to turn off the alarm sound 

ADVANCED MANAGEMENT 

 

N.B. 

The instructions below are reserved for 

specialised technical assistance 
personnel. 

8.1.3.9 Different operating mode start conditions 

Each operating mode must comply with precise 

conditions: 

 

AUTOMATIC

 operating mode 

The condition to enable the start of this function is: 
lower thermistor< SP2 

– r0 (hysteresis); 

 

ECO 

operating mode 

The condition to enable the start of this function is: 
lower thermistor< SP1 

– r0 (hysteresis); 

 

OVERBOOST 

operating mode 

The condition to enable the start of this function is: 
lower thermistor< SP3 and upper thermistor< SP3. 
As soon as a temperature exceeding SP3 has been 
detected, the Overboost operating mode terminates 
and the previously set operative mode is restored.  

 

8.1.3.10 The display 

If the equipment is in the “ON” status during normal 

operation, the display will show the established 
temperature by means of parameter P5: 

 

If P5 = 0, the display will show the temperature of 
the upper part of the boiler; 

 

If P5 = 1, the display will show the active working 
set point; 

 

If P5 = 2, the display will show the temperature of 
the lower part of the boiler; 

 

If P5 = 3, the display will show the temperature of 
the evaporator; 

 

If the equipment is in the “stand-by” mode, the 
display will be switched off.

 

 

 

Содержание RKHH2E200AAV33

Страница 1: ...Installation Manual Installation manual Domestic Hot Water Heat Pump Monobloc type RKHH2E200AAV33 RKHH2E260AAV33 RKHH2E260PAAV33 Domestic Hot Water Heat Pump Monobloc type English...

Страница 2: ......

Страница 3: ...RKHH2E P AAV33 ROTEX Domestic Hot Water Heat Pump 2018 8 Installation manual 3...

Страница 4: ...ing limits 16 5 5 Fundamental safety rules 16 5 6 Information on coolant used 16 6 Installation and connections 17 6 1 Preparation of the installation site 17 6 2 Ventilation connection 17 6 2 1 Parti...

Страница 5: ...ead the service manual For more information see the installer and user reference guide 1 2 For the user If you are not sure how to operate the unit contact yourinstaller This appliance can be used by...

Страница 6: ...o NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are preferably carried out under dry weather conditions to avoid...

Страница 7: ...ssor breakdown do NOT charge more than the specified amount of refrigerant When the refrigerant system needs to be opened refrigerant must be treated according to the applicable legislation WARNING Ma...

Страница 8: ...a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure t...

Страница 9: ...to the unit Installation manual Instruction manual designed for a certain unit or application explaining how to install configure and maintain it Operation manual Instruction manual designed for a ce...

Страница 10: ...able to instructions figures drawings or descriptions without prejudice to errors of any kind The Supplier shall not be held responsible for damages attributable to misuse improper use or as a consequ...

Страница 11: ...power etc Version Configuration description RKHH2E200AAV33 RKHH2E260AAV33 Air source heat pump for the production of domestic hot water RKHH2E260PAAV33 Air source heat pump for the production of domes...

Страница 12: ...t of a structural nature WARNING The equipment can be transported horizontally only during the last km following the instructions in the section Positions permitted for transporting and handling above...

Страница 13: ...160 mm 13 Hermetically sealed rotary compressor 14 Replaceable magnesium anode 15 1 5 kW 230 W Electric heating element 16 Condenser pump discharge line 17 Condenser return 18 Replaceable magnesium a...

Страница 14: ...element power kW 1 5 1 5 1 5 Maximum current in HP A 2 4 2 4 2 4 Required overload protections A 16A T fuse 16A automatic switch characteristic C to be expected during installation on power supply sys...

Страница 15: ...Mg anode 26x250 mm 1 x Mg anode 26x250 mm 1 x Mg anode 26x400 mm Insulation 50 mm high density polyurethane foam Defrosting Active with Hot Gas valve Dimensions mm H1714xD600xDmax650 H2000xD600xDmax6...

Страница 16: ...ate functional monitoring system with alarm functions in order to avoid such damage being caused Moreover it is necessary to arrange for a back up service in case of failure 5 4 Operating limits The a...

Страница 17: ...r connection to the condense drain Be available and ready with adequate discharge pipes in case of damage caused to the boiler or actuation of the safety valve or breakage of pipes connections Have co...

Страница 18: ...ickness Sound mufflers can be mounted when deemed necessary Fit the pipes the holes in the wall and the connections to the heat pump with vibration damping systems WARNING The simultaneous operation o...

Страница 19: ...ersions A B C D E F G mm mm mm mm mm mm mm 650 1714 600 160 1101 795 H I J K L M N mm mm mm mm mm mm mm 70 150 380 195 O P mm mm 337 5 10 6 4 Water supply connections Connect the cold water inlet and...

Страница 20: ...rol device of the check valve a safety valve and a device to interrupt the water load Fig 8a N B The drain pipe connected to the equipment for protection against overpressure must be installed sloping...

Страница 21: ...n via siphon with water shut off valve 6 5 Solar power system integration Fig 10 is an example of solar power system integration Cold water intake pipe Solar power system pump and accessories Solar co...

Страница 22: ...e brown yellow and the water temperature measured by lower thermistor is higher than SP8 the heat pump stops and water is heated by the solar panels The heat pump restarts when the contact stops and t...

Страница 23: ...fication plate The commissioning procedure should be completed by following these steps Fill the boiler by connecting the water inlet tap and check for any leaks from gaskets and connections Tighten t...

Страница 24: ...Stand by mode In the stand by mode the instrument can automatically switch on at certain time slots and independently enables the anti Legionella and defrosting functions When the equipment is switch...

Страница 25: ...een finished the function is automatically disabled and the equipment is automatically restored to the Automatic or Economy mode depending on which one was previously set by the user ANTI LEGIONELLA o...

Страница 26: ...keyboard follow this procedure Make sure that no other advanced procedures are in progress Press and hold the and the keys until Loc will appear on the display for 1 second If the keyboard is locked i...

Страница 27: ...slot operation in order to avoid malfunctions caused by users 8 1 3 7 Display of the operating status Make sure that the keyboard is not locked paragraph 0 and that no other advanced procedures are in...

Страница 28: ...ivation See parameters i0 i1 18 and i9 Switch off the equipment and restart it or disconnect the equipment from the mains power supply Main consequences Compressor will be switched off Defrosting will...

Страница 29: ...ngs Make sure that the keyboard is not locked paragraph 0 and that no other advanced procedures are in progress Press and release the key the first available code will appear on the display Press and...

Страница 30: ...ures are in progress Press and hold the and keys for 4 seconds PA password will appear on the screen Press and release the key Press and release either the or the key within the next 15 seconds to set...

Страница 31: ...the compressor and consequently lead to breakdown of the equipment At every Start up the fan is activated for an amount of time set by parameter C12 1 minute After this amount of time the system meas...

Страница 32: ...Lower thermistor calibration CA2 C F 25 0 25 0 0 0 Evaporator thermistor calibration CA3 C F 25 0 25 0 0 0 Thermistor type P0 0 1 1 0 PTC 1 NTC 2 PT1000 Decimal point P1 0 1 1 1 Display decimal point...

Страница 33: ...r stopped Evaporator temperature to conclude defrosting procedure only if P4 1 d2 C F 50 0 50 0 3 0 Maximum duration of defrosting procedure d3 min 0 99 8 Automatic defrosting start threshold evaporat...

Страница 34: ...for digital input alarm counter reset i9 min 1 999 240 Buzzer enabling u9 0 1 1 0 Buzzer disabled 1 Buzzer enabled Switching on time for Monday Hd1 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for...

Страница 35: ...RKHH2E P AAV33 ROTEX Domestic Hot Water Heat Pump 2018 8 Installation manual 35 Parameter description Code U M Min Max Default Notes 1 ODD 2 EVEN RESERVED E9 0 2 0...

Страница 36: ...necessary to Disconnect the device from the mains power supply Remove any air ducts see paragraph 0 Remove the upper cover by undoing the appropriate locking screws Fig 18 Manually reset the tripped...

Страница 37: ...ctrochemical potential in comparison to the material that coates the inside of the boiler It therefore attracts the negative charges that are formed during the heating of the water and would cause the...

Страница 38: ...regulations WARNING This equipment contains greenhouse fluorinated gas included in the Kyoto protocol The maintenance and disposal operations must only be carried out by qualified personnel INFORMATIO...

Страница 39: ...mperature settings of the water heater C 55 Sound power level Lwa indoors in dB dB 53 The water heater is able to work only during off peak hours NO Any specific precautions that shall be taken when t...

Страница 40: ......

Страница 41: ......

Страница 42: ...r im Ausland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani...

Отзывы: