8-44
Operating modes:
To support the full range of available combination options in multivalent heating
systems with buffer support, the control system offers the possibility to set various
operating modes for buffer operation. The different settings cause different
processing sequences of heat requests for heating circuits and hot water. In the
following, the different operating modes are illustrated using exemplary hydraulics
layouts.
Operating mode 1 – Charging control HC and DHW requests
System hydraulics:
Heating-circuit and hot-water control send their demand value to buffer control.
Buffer control requests additional energy from the heat generator via the buffer
loading pump.
See the table below for detailed correlations.
Operating mode 2 – Loading control for HC request only
System hydraulics:
Heat
generator
Buffer
BS
BURN 1
BULP
OS
BU
HC-P
L
VF1
VF2
MC2
MC1
SOL-P
Domestic hot
water
tank
DHWS
BU-2
BS
BURN1
BULP
OS
HC
BU
VF1
VF2
MC1
MC2
BU-2
DHWS
SOL-P
Heat
generator
Buffer
Domestic hot
water
tank
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...