Product documentation THETA NORM/UNIT
8-25
Example:
Maximum temperature setting for the heating circuit = 40 °C
1. Day:
constant heating at 25 °C
2. Day:
constant heating at 30 °C
3. Day:
constant heating at 35 °C
4. Day:
constant heating at 40 °C
5.-15. Day:
constant heating at maximum flow temperature
16. Day:
reduced heating at 35 °C
17. Day:
reduced heating at 30 °C
18. Day:
reduced heating at 25 °C
On the start day heating at 25 °C is maintained till midnight. The heating function for floor covering sets in
at 00:00 h on the following day.
Time profile of the screed function for floor cover heating
Step 1+2: Function heating with subsequent floor cover heating (setting 3)
Both steps are carried out subsequently.
Time profile of the screed function for function heating and heating for floor covering
Prior to activation of the screed function it must be ensured that the screed to be
heated has dried appropriately.
Cement screed:
21 days
Calcium sulfate
(anhydride) screed:7 days
T
VLSet
[°C]
ST
t
[Days]
T
VLSet
ST
t
[Days]
T
VLSet
[°C]
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...