EbV
Product documentation THETA NORM/UNIT
9-7
9.3
Expanding the system by several standard units
9.3.1
Examples with several controllers
Example 1:
Heating system with 2 stage heat generator, DHW control, and 4 mixed circuits. The
following diagram shows the hydraulic system.
The following components will be connected to the first controller with busadress 10:
• Outdoor sensor
• Stage 1 and 2 of the burner
• Boiler sensor
• DHW sensor
• Domestic hot water charging pump
• Mixer pump, mixer open / closed and flow sensor of heating circuit 1
• Mixer pump, mixer open / closed and flow sensor of heating circuit 2
The following components will be connected to the second controller with busadress
20:
• Mixer pump, mixer open / closed and flow sensor of heating circuit 3
• Mixer pump, mixer open / closed and flow sensor of heating circuit 4
Boiler
DHW tank
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...