Accura 2350-DCM User Guide
Chapter 2 Accura 2350-DCM Operation/Setup
ⓒ
2018 Rootech Inc. All Rights Reserved
Page 31
Auto Clear Time of Event Alarms
Auto Clear Time
Description
InF[default]
Infinite: disables the Auto clear function
1
–
999 [min]
Can be set from 1 minute to 999 minutes in one-minute increments
DO Type
DO Type
Description
Lat[default]
Latch
PL.P
Periodic Pulse
PL.U
Uncountable Pulse
PL.C
Countable Pulse
DO Polarity
DO Polarity
Description
nrM[default]
Normal polarity. The output contact is closed by the command 1 and is
open by the command 0
rEu
Reverse polarity. Open by command 1, closed by command 0
DO Pulse Period
DO Pulse Period
Description
[d][d].[d]
1
0.2
–
65.5 seconds / 0.1 seconds step
Default: 0.2 seconds
1. d
→
decimal number
DO Pulse On-Time
DO Pulse On-time
Description
[d][d].[d]
1
0.1
–
65.5 seconds / in steps of 0.1 seconds
Default: 0.1 seconds
1. d
→
decimal number
Manual DO Control
The manual control of DOs is enabled only when the linked operation of the DOs of all channels is set
to "Off". The screen shown below is not supported when the linked operation of the DO is set to
“On”
.
DO Control
Description
0 [_]
1
Displays the status of DO contact for the command 0
1 [o]
1
Displays the status of DO contact for the command 1
1. The open contact is indicated as the underlined symbol
“
_”
and the closed contact is indicated as the
lowercased symbol "o". The DO contact operates according to the DO polarity settings.