Accura 2350-DCM User Guide 

Appendix A Specifications 

 

  2018 Rootech Inc. All Rights Reserved 

Page  37 

 

Maximum measured value 

DC 100 A 

 

Temperature drift 

8

 

±

0.02% FS/

  typ. 

Based on the calibration temperature of 25

 

Power / Energy Measurement 

Aggregation of 
measurement data   

Aggregates Power/Energy measurement data for 0.5 seconds 

5

 

Accuracy 

±

1.0% RD 

±

0.15% FS 

Based on voltage/current measurement accuracy 

Event

 

Number of event channels 

5 (channel 1,2,3,4,5) 

 

Event type 

Off / Over 

9

 / Under 

10

 Selectable (default: 

Off) 

Setup for each channel 

Monitored signal 

Voltage / Current Selectable 

Setup for each channel 

Operation linked with   

Digital Output   

DO operation mode when an event occurs 
Disable / Enable 

Setup for each channel 

Time resolution 

20 ms 

Aggregates voltage and current data 

4

 for 20 ms   

Event data 

Duration time, Max/Min value 

Stored in non-volatile memory 

 

Waveform data measured for 1.5 
seconds (20 ms time resolution) 

Stored in volatile memory 

Digital Output[DO]

 

Terminal name 

DO, DO

G

 

 

Connector type 

Screw-type terminal 

 

Wire specification   

0.13 to 2.08 mm2 (26 to 14 AWG), copper or aluminum

 

Output type 

11

 

Latch, Periodic Pulse, Uncountable Pulse, Countable Pulse 

12

 

Min pulse period 

0.2 sec 

 

Min pulse on-time 

0.1 sec 

 

Isolation 

AC 2,000 V for 1 minute 

 

Maximum rating 

AC/DC 400 V 350 mA (max. 1A)

 

 

General

 

Weight 

242 g 

Excluding the mounting wings L/S   

245 g 

Including the mounting wings L/S 

Operating temperature 

-20 to 70 

C (-4 to 158 

), 

Safe operating 
temperature 

16

 

-20 to 65

C (-4 to 149 

), 

Storage temperature 

-20 to 85

C (-40 to 185 

), 

Operating humidity 

5 to 95 % (non-condensing), 

Operating altitude 

Up to 2,000 m 

1. The power source side and the load side are indicated as S and L, respectively.   

Connections should be made properly according to the indicated po/-). When the polarity is connected in 

reverse, voltage and current are measured as negative values. 

2. The DCM-50V module receives control power via DC busbar voltage in case of a stand-alone operation. 

3. The number of DCM modules that can be connected to Accura 2300[S] is limited to 10 (5 modules connected to each 

Содержание ACCURA 2350-DCM

Страница 1: ......

Страница 2: ...have received appropriate training for high voltage and current devices Caution If hazardous voltages are mishandled while installing and operating the product in the field it can cause serious injury...

Страница 3: ...tions and the manual before making orders In the absence of written agreements Rootech Inc assumes no liability for applications assistance customer s system design or infringement of patents or copyr...

Страница 4: ...or the product Rootech will decide at its discretion whether to repair or replace it or give a refund for the product for when the warranty period for the product expired or issues related to the prod...

Страница 5: ...ginal purchaser is responsible for determining the feasibility of such suggestions and should conduct tests to prove their feasibility It is the original purchaser s responsibility to determine the su...

Страница 6: ...wer energy measurement accuracy 1 10 October 18 2018 Added Accura 2350 DCM 500V 80A module 1 20 December 24 2018 Added a note for the number of connectable devices Changed the temperature drift to 0 0...

Страница 7: ...evice Configuration and Operation 14 Voltage Connection and Control Power Supply 14 Measurement and Event 15 Digital Output DO 23 Button Operation 24 LCD Screen 26 Operation Mode 26 Display 26 Event A...

Страница 8: ...for 20 ms 17 Fig 2 3 Data Aggregated for 0 5 s 17 Fig 2 4 Event Block Diagram 18 Fig 2 5 Event Alarms via DOs 19 Fig 2 6 Occurrence of Over Event Clearing Alarms with the SET button after the event en...

Страница 9: ...ice setup on the LCD screen of Accura 2300 S Accura 2300 and Accura 2300S have no functional differences in their operation with the DCM module However the sequence of their LCD screens and display se...

Страница 10: ...apter 1 Installation and Wiring Accura 2350 DCM User Guide Page 10 2018 Rootech Inc All Rights Reserved Dimensions Fig 1 2 Accura 2350 DCM Front Fig 1 3 Accura 2350 DCM Rear Fig 1 4 Accura 2350 DCM Si...

Страница 11: ...Installation and Wiring 2018 Rootech Inc All Rights Reserved Page 11 Installation Panel Mounting Fig 1 5 Panel Mounting Place the DCM module in its intended position on the panel Insert the screws int...

Страница 12: ...Power Supply Connection The DCM module measures the voltage between the bus bars and the current that flows through the bus bar It is possible to use both and bus bars and only the bus bar when makin...

Страница 13: ...control power through the communication line cable When Accura 2350 DCM 50V module operates alone it receives control power via the DC voltage busbar Fig 1 8 Communication Cable Connection Note The p...

Страница 14: ...ly Supplied from Accura 2300 S with the RJ12 communication line Bus bar 2 DC 12 55 V Accura 2350 DCM 50V Stand alone operation Power consumption 125mA when connected to Accura 2300 S with the RJ12 com...

Страница 15: ...00V Current Measurement Sampling time 1 ms Aggregation of measurement data Aggregates data every 20 ms 1 based on the data measured over 1 ms Window aggregation 1 32 ms default 20 ms Aggregates data e...

Страница 16: ...d are also provided Refer to the aggregation section of Accura 2300 S User Guide for details 3 The minimum DC voltage for the stand alone operation of the DCM 50V module is 12V 4 The measured value be...

Страница 17: ...20 Over Under voltage and current events are detected with the data generated every 20 ms Fig 2 2 Data Aggregated for 20 ms N window 20 ms 20ms aggregation data 1ms sampling data 1 ms Data Aggregated...

Страница 18: ...hen the measured value is above the threshold 2 value but is below the threshold 1 value and the value is maintained during the set delay time Hysteresis If the measured value frequently rises above o...

Страница 19: ...en an event occurs users can reset DOs with the SET button Generation of Event Alarms Event alarms are provided to notify users of the occurrence of events When an event occurs the event LED and the L...

Страница 20: ...VENT button on Accura 2300 S If you confirm the event log with EVENT button of Accura 2300 S event alarm of Accura 2300 S and event alarm of DCM module are also cleared However releasing the event ala...

Страница 21: ...er the event ends event duration threshold level Button clear Pickup signal Start Event End Event Button Clear Event LED DO latch DO pulse with hysteresis Voltage Current time delay end event start ev...

Страница 22: ...value is below the residual level An Under event does not occur if the measured value falls below the residual level from normal state within the delay time When the residual level is set to 0 Under e...

Страница 23: ...After completion of the pulse in progress pulse generation is stopped Uncountable Pulse 1 A single pulse occurs on the closed contact The command issued after the occurrence of a single pulse is clear...

Страница 24: ...alarms or to check or change setup items Clearing Event Alarms Button Function Display screen Displays the module ID and measured values in sequence Event Alarm The screen automatically switches to th...

Страница 25: ...he setup value changes sequentially each time the button is pressed Long press Return to the setup screen and save the selected setup value And then the screen stops blinking If there is the next digi...

Страница 26: ...screens appear in the following sequence Short press the SET button on the display mode to move to the setup mode ID 1 Volt Curr Power 2 DO Status Temperature 3 1 If the DCM 50V module performs a sta...

Страница 27: ...according to the indicated polarity When reverse polarity occurs voltage and current are measured as negative values DO Status Display DO Status 2nd row Displays the status of the output contact with...

Страница 28: ...Under Event 1 d decimal number 2 Blinks with the Event LED to notify users of the occurrence of events End Event Display If end event occurs after start event the maximum value and the event duration...

Страница 29: ...his screen is not available if the event type of all channels is set to Off 4 The manual control of DOs are enabled only when the linked operation of the DO for each event channel is set to Off This s...

Страница 30: ...the threshold 2 Above 0 1 d decimal number The Residual level is only available for an Under event An Under event occurs when the measured value falls below the start level threshold 1 and is over th...

Страница 31: ...mand 0 DO Pulse Period DO Pulse Period Description d d d 1 0 2 65 5 seconds 0 1 seconds step Default 0 2 seconds 1 d decimal number DO Pulse On Time DO Pulse On time Description d d d 1 0 1 65 5 secon...

Страница 32: ...CD screen of Accura 2300S The LCD screen of Accura 2300 is similar to that of Accura 2300S Users can perform the following functions with the buttons ESC SETUP EVENT ENTER on the front of Accura 2300...

Страница 33: ...asured values of Accura 2300S and the selected Accura 2350 module are displayed The measured values of the DCM module are displayed in the MODULE column Column Volt Curr Power Energy V I P E Voltage F...

Страница 34: ...ccura 2300 S detects the DCM module s start event and the Event LED and LCD backlight blink when the event occurs Users can enter the event log mode by long pressing the EVENT button on Accura 2300 S...

Страница 35: ...Under event the end event of Over or Under event 4th row Start event measured voltage or current value when the signal is picked up End event the maximum value of voltage or current measured during t...

Страница 36: ...e Measurement Sampling time 1 ms Aggregation of measurement data Aggregates data for 20 ms 4 based on the data measured over 1 ms Window aggregation 1 32 ms default 20 ms Aggregates data for 0 5 secon...

Страница 37: ...atile memory Digital Output DO Terminal name DO DOG Connector type Screw type terminal Wire specification 0 13 to 2 08 mm2 26 to 14 AWG copper or aluminum Output type 11 Latch Periodic Pulse Uncountab...

Страница 38: ...r periodically on the closed contact 0 After completion of the pulse in progress pulse generation is stopped Uncountable Pulse 1 A single pulse occurs on the closed contact The command issued after th...

Страница 39: ...ix B Ordering Information 2018 Rootech Inc All Rights Reserved Page 39 Appendix B Ordering Information Module Name Accura 2350 DCM 50V 80A DC Voltage Current Rating 50V 80A Accura 2350 DCM 500V 80A DC...

Страница 40: ...rchasing inquiries www rootech com sales rootech com 2018 Rootech Inc All Rights Reserved Accura 2300 2350 Accura 2300S 2350 Accura 2700 2750 Accura 3000 Accura 3300E Accura 3300S 3300 Accura 3500S 35...

Отзывы: