Accura 2350-DCM User Guide
Chapter 2 Accura 2350-DCM Operation/Setup
ⓒ
2018 Rootech Inc. All Rights Reserved
Page 19
configured to operate when an event occurs, commands are issued to the DO channels.
End event
An end event occurs when the measured value falls back to the threshold value set for detection
of an end event after a start event occurs. monitoring signal is recovered within the end level
with the start event occurring,. The event LED is not turned off only when users press the SET
button. If DO channels are configured to operate when an event occurs, users can reset DOs with
the SET button.
Generation of Event Alarms
Event alarms are provided to notify users of the occurrence of events. When an event occurs, the event
LED and the LCD screen indicating event data blink. Alarms can also be generated via DO contacts.
Alarm settings can be configured for each DO channel, and the setting is disabled by default.
Event Alarm
Description
Operation
Event LED
Blinks every 0.2 sec
Basic event alarm
LCD screen
Event type Indication Character blinking every 0.4 second
Basic event alarm
Digital output
Outputs alarms via contacts (latch or pulse configurable)
Operation enabled via settings
Fig 2.5 Event Alarms via DOs
Event 1 DO
Event 2 DO
Event 3 DO
Event 4 DO
Event 5 DO
Event DO