Accura 2350-DCM User Guide
Chapter 2 Accura 2350-DCM Operation/Setup
ⓒ
2018 Rootech Inc. All Rights Reserved
Page 29
Setup Mode
Each time the SET button is short pressed, the next setup menu is selected. Press the SET button twice
shortly to select the setup menu in the reverse direction.
ID
1
Channel 1
Event Type
2
Channel 1
Threshold
Channel 1
Threshold 2
3
Channel 1
Time Delay
Channel 1
Linked DO
Operation
Channel 2
Event Type
2
Channel 3
Event Type
2
DO
Control
4
DO
On-Time
DO
Pulse Period
DO Polarity
DO Type
Event Auto
Clear Time
4
Channel 5
Event Type
2
Channel 4
Event Type
2
1. If the DCM-50V module is in stand-alone operation, the ID screen is not available.
2. If the event type of a channel is set to
“
Off
”
, the other setup screens of the channel are not available.
3. This screen is only supported when the event type is set to
“
Under
”
. When the threshold 2 is set to a value
abnormally above the threshold, the threshold 2 value is regarded as zero.
4. This screen is not available if the event type of all channels is set to "Off".
4. The manual control of DOs are enabled only when the linked operation of the DO for each event channel is set to
"Off". This screen is not available when the linked operation of the DO is set to
“On”
.
Note
If there is no button operation for 10 seconds on the setup screen, the screen automatically returns to the
display screen.
If there is no button operation for 25 seconds on the screen where changes can be
made to settings, the screen automatically returns to the display screen.
ID Setup
If the DCM-50V module is in stand-alone operation, the module ID screen is not displayed.
ID
Module ID
[d][d]
1
DCM Module ID
2
Default 255
Setup range: 0 - 39
1. d
→
decimal number.
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2350
modules as a factory default value.
Module ID
ID
Description
Communication ID ID 0 - 39
ID of Accura 2350 module that enables communication
Conflict ID
Redundant IDs
There are more than 2 identical IDs. communication unavailable
Standby ID
ID 255
Module ID for checking connection status, communication unavailable
Содержание ACCURA 2350-DCM