6.
Installation and Setup Guidelines
•
The PR311-BK reader should be mounted near the supervised door on a vertical
piece of supporting structure.
•
Assure that the surface beneath of the controller’s rear panel is flat and smooth,
especially in the area where tamper sensor will contact a surface of the wall.
•
Disconnect power supply before making any electrical connections.
•
For installations on a metal surface, place a non-metallic min. 10 mm thick
spacer (a plastic/plaster plate etc.) between the reader and the supporting
structure.
•
For installations with two readers to be mounted on opposite sides of the same
wall and aligned along the same geometrical axis, place a metal plate (2-4 time
bigger is size then a reader) between them and make sure none of them has
direct contact with it (allow min. 10 mm space between reader and metal plate).
This measure is intended to isolate magnetic fields generate by both readers. If
the readers are not adequate separated it may occur that card presented for a
first reader will be read on the second one.
•
For best results mount the proximity readers at least 0.5 m apart.
•
When using separate power supply sources, connect all power supply negative
(–) leads together. This rule is not valid for power sources used for supply of a
door lock. Always assure that supplies used to power electronics and door locks
are electrically separated.
•
Roger recommends grinding the negative (–) lead of a power supply. Connection
to the earth should be arranged in one arbitrary selected point.
•
With its relatively weak electromagnetic field generation, the terminal should not
cause any harmful interference to operation of other equipment. However, its
card reading performance can be affected by other interference generating
devices, esp. radio waves emitting equipment or CRT computer monitors.
•
If card reading performance of the controller deteriorates (e.g. reduced reading
range or incorrect readings) consider reinstallation in a new location.
•
Once installed and electrically connected, the reader has to be properly
configured. The programming can be carried out either through manual method
or from PC. A new factory unit is delivered with preprogrammed MASTER card
and with address set to ID=00.
•
When lost, MASTER cards can be reprogrammed to a reader anew, any EM 125
kHz card can be programmed as a MASTER.
•
It is strongly recommended to program the controller form one source only:
from PC program or manually. When both methods are used to the same unit it
may result in some confusion (e.g. new user added manually will not exist in PC
program).
•
When controller is intended to be managed from PC only you don’t have to
program any MASTER card, just program ID address of the unit and connect it to
the computer.
•
When controller operates in an
Integrated Access Control System
it must be
connected to RS485
Communication Bus
.