74
Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
PowerFlex DC Drive and Field Controller Technical Data
PowerFlex DC Field Controller Specifications
(continued)
IP20 NEMA/UL Type Open Watts Loss
Watts loss and cooling fan attributes data that are shown in the following tables is based on the rated current of the drive.
PowerFlex DC Drives, Frame A
Category
Specification
Inputs
Analog Inputs
Three configurable, isolated, differential
±10V, 0…10V, 0…20 mA or 4…20 mA.
Resolution: 11 Bit + sign
Digital Inputs
Eight standard configurable, four additional configurable with the I/O Expansion circuit board.
Max V30V DC input, 200 mA (total current draw is the sum of encoder power, digital outputs, and any
other loads that are connected to terminal 19)
Outputs
Analog Outputs
Two standard configurable, two additional configurable with the I/O Expansion circuit board. Sample rate 2
ms.
±10V, 5 mA, bipolar (current is not bipolar)
Resolution: 11 Bit + sign
Digital Outputs
Four standard configurable, four additional configurable with the I/O Expansion circuit board.
30V, 50 mA
Relay Outputs
Two configurable, N.O. contacts
Max. 250V AC, 1 A AC1
Drive Current Rating Code
(1)
(1) See
PowerFlex DC Drive Catalog Number Explanation on page 6
, positions 8…10 for corresponding drive Hp rating, armature Amp rating, and field Amp rating.
Total Watts
Loss
Total Value for Fan
@ 230V AC
@ 460V AC
AC Input Voltage
Rated Current (A)
Max. Airflow
Noise Level
7P0
4P1
131
(No fan)
9P0
6P0
012
010
020
014
—
019
029
027
186
038
035
254
(Internal power supply)
80 m
3
/h
37 dB(A)
055
045
—
052
073
073
408
160 m
3
/h
45 dB(A)
093
086
476
110
—
—
100
553
129