Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
73
PowerFlex DC Drive and Field Controller Technical Data
PowerFlex DC Field Controller Specifications
Category
Specification
Agency Certification
c-UL-us
Listed to UL508C and CAN/CSA C22.2 No. 14-05.
CE
In conformity with the following European Directives:
• EMC Directive (2004/108/EC)
• Low Voltage Directive (2006/95/EC)
Standards applied:
• EN 50178
• EN 61800-3
RCM
Certified by Rockwell Automation to be in conformity with the requirements of the applicable Australian legislation and the
standards referenced: IEC 61800-3.
Korean KC
Registration
MSIP-REM-RAA-20P
See the certificate of registration for specific drive catalog numbers that have this certification.
(1)
(1) See the product certifications website,
http://www.rockwellautomation.com/rockwellautomation/certification/overview.page
for declarations of conformity, certificates, and other
certification details.
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
Category
Specification
Drive Type
Full Wave Regen, 6 Pulse, Regulated Field Supply
Protection
Heat sink Thermistor:
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Programmable, 0…250% of rated current (175% default)
Line transients
Up to 2,000 volts peak per IEC 6100-4-5
Control Logic Noise Immunity
Showering arc transients up to 1500V peak
Power Ride-Thru
15 milliseconds at full load
Logic Control Ride-Thru
0.5 seconds minimum, 2 seconds typical
Environment
(1)
(1) Field controllers must be installed in a Pollution Degree 2 environment.
(2) 115V AC input control power requires a jumper between terminals SA and SB for frame B field controllers only. For more information, see
PowerFlex DC Drives and Field Controller Control
Circuit Input Power on page 36
Altitude:
1000 m (3300 ft) max. without derating.
De-rate output power by 1.2% for every 100 meters (328 ft) above 1000 meters (3300 ft).
Maximum Surrounding Air
Temperature IP20, NEMA Type
Open:
0…50 °C (32…122 °F), typical.
De-rate 1.25% for every 1 °C over 50 °C (122 °F), to 55 °C (131 °F).
More cooling is required for temps. above 55 °C.
Storage Temp. (all const.)
–25…+55 °C (–13…+131 °F)
Atmosphere
Important:
The field controller
must
not
be installed in an area where the ambient atmosphere contains
volatile or corrosive gas, vapors, or dust. If the drive is not going to be immediately installed, it must be stored
in an area where it is not exposed to a corrosive atmosphere.
Relative Humidity
Operating: 5…85% noncondensing
Storage: 5…95% noncondensing
Shock
15G peak for 11 ms duration (°1.0 ms)
Vibration
0.152 mm (0.006 in.) displacement, 1G peak
Electrical
Input Voltages:
Control: 115V AC or 230V AC +/- 15%, 1 Phase
(For details, see
.)
Input Frequency:
50/60 Hz +/- 5%
Max. Rate of Change of Input
Frequency:
2 Hz/s
Output Current:
17…570 A
Drive Overload Capability:
100% rated continuous current
Field Output Voltage
Maximum field output voltage is 1.16 x AC input line voltage.
Max. Short Circuit Rating:
100,000 A