56
Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
PowerFlex DC Drive and Field Controller Technical Data
Frame C Regenerative Drive - Leg Fuse Location
Frame D Regenerative Drive - Leg Fuse Location
Leg Fuses - 690V AC Input Frame C Drives
Frame Drive Current
Rating Code
DC
Amps
AC Line
Amps Qty
Bussmann
Mersen
SIBA
Square Body - Flush End Contact
C
452
452
369
6
17 switch 170H0069
12,5 URD 72 TTF 0500 + switch MS 3V 1-5 BS
20 771 32.500 + switch 28 001 04
565
565
461
—
12,5 URD 72 TTF 0630 + switch MS 3V 1-5 BS
20 771 32.630 + switch 28 001 04
Leg Fuses - 690V AC Input Frame D Drives
Frame Drive Current
Rating Code
DC
Amps
AC Line
Amps
Qty
Bussmann
Mersen
SIBA
Square Body - DIN 43653 Stud-Mount
D
678
678
553
6
17 switch 170H0069
G switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
791
791
645
17 switch 170H0069
J switch MS 3V 1-5 UR
20 735 32.800 + switch 28 001 04
904
904
738
17 switch 170H0069
K switch MS 3V 1-5 UR
20 735 32.900 + switch 28 001 04
1K0
1017
830
17 switch 170H0069
L switch MS 3V 1-5 UR
20 735 32.1000 + switch 28 001 04
1K1
1130
922
12
17 switch 170H0069
G switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
1K2
1243
1014
17 switch 170H0069
G switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
1K4
1413
1153
17 switch 170H0069
H switch MS 3V 1-5 UR
20 735 32.700 + switch 28 001 04
1K5
1582
1291
17 switch 170H0069
J switch MS 3V 1-5 UR
20 735 32.800 + switch 28 001 04
Note: Drive shown with front covers removed and
Control EMI shield lowered.
Leg fuses and switches are on the busbars behind the Control EMI shield,
which holds the Control board.
Note: Drive shown with Control EMI
shield in open position.
Leg fuses and switches are on the busbars behind the Control EMI shield,
which holds the Control board.