70
Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
PowerFlex DC Drive and Field Controller Technical Data
PowerFlex DC Drive Specifications
Category
Specification
Agency Certification
c-UL-us
Listed to UL508C and CAN/CSA C22.2 No. 14-05.
CE
In conformity with the following European Directives:
• EMC Directive (2014/35/EU)
• Low Voltage Directive (2006/95/EC)
Standards applied:
• EN 61800-5-1
• EN 61800-3
RCM
Certified by Rockwell Automation to be in conformity with the requirements of the applicable Australian legislation and
the standards referenced: IEC 61800-3.
Korean KC
Registration
MSIP-REM-RAA-20P
See the certificate of registration for specific drive catalog numbers that have this certification.
(1)
(1) See the product certifications website,
http://www.rockwellautomation.com/products/certification/
for declarations of conformity, certificates, and other certification details.
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
Category
Specification
Drive Type
Full Wave Regen, 6 Pulse, Regulated Field Supply
Protection
Heat sink Thermistor:
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
• Software Overcurrent Trip:
• Hardware Overcurrent Trip:
• Programmable, 0…250% of rated current (175% default)
• Based on armature circuit fusing
Line transients:
Up to 2000 volts peak per IEC 6100-4-5
Control Logic Noise Immunity:
Showering arc transients up to 1500V peak
Power Ride-Thru:
15 milliseconds at full load
Logic Control Ride-Thru:
0.5 seconds minimum, 2 seconds typical
Environment
(1)
(1) PowerFlex DC drives must be installed in a Pollution Degree 2 environment.
Altitude:
1000 m (3300 ft) max. without derating.
De-rate output power by 1.2% for every 100 meters (328 ft) above 1000 meters (3300 ft).
Maximum Surrounding Air
Temperature IP20, NEMA Type Open:
0…50 °C (32…122 °F), typical.
De-rate 1.25% for every 1 °C over 50 °C (122 °F), to 55 °C (131 °F).
More cooling is required for temps. above 55 °C.
Storage Temp. (all const.):
–25…+55 °C (–13…+131 °F)
Atmosphere:
Important:
Drive
must
not
be installed in an area where the ambient atmosphere contains volatile
or corrosive gas, vapors, or dust. If the drive is not going to be immediately installed, it must be
stored in an area where it is not exposed to a corrosive atmosphere.
Relative Humidity:
Operating: 5…85% noncondensing
Storage: 5…95% noncondensing
Shock:
15G peak for 11 ms duration (±1.0 ms)
Vibration:
0.152 mm (0.006 in.) displacement, 1G peak