Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
31
PowerFlex DC Drive and Field Controller Technical Data
Frame C Armature Terminal Block Locations
Frame D Armature Terminal Block Locations
Armature Power Terminal and Ground (PE) Wire Sizes
Frame
Drive Current Rating Code
(1)
(1) See
PowerFlex DC Drive Catalog Number Explanation on page 6
, positions 8, 9 and 10 for corresponding drive Hp rating, armature Amp rating, and field Amp rating.
Terminals
Wire Size and Type
Terminal Bolt Size
(mm)
Final Torque
N•m (lb•in)
230V
460V
575V
690V
A
7P0…055
4P1…052
—
—
U, V, W, C, D, PE
See Cable and Wiring
Recommendations in the
PowerFlex Digital DC Drive
User Manual, publication
.
5
6 (53)
073…110
073…129
Terminal Block
12 (106)
B
All
All
U, V, W, C, D
10
25 (221)
PE
8
15 (132.75)
C
U, V, W, C, D
10
25 (221)
PE
8
15 (132.75)
D
All
All
U, V, W, C, D, PE
12
45 (398.2)
IMPORTANT
Certain frame D drives require the use of a terminal adapter kit for terminals U, V, W, C, and D. For details, see
D Terminal Adapter Kits on page 20
.
Bottom View
Front View
PE
U
C
V
D
W
Top of Drive
Bottom of Drive
IMPORTANT
Certain frame D drives require the use of a terminal adapter kits for terminals U, V, W, C and D. See Frame D
for details.
PE
U
C
V
D
W