2 Transport and positioning
18
Table 1�2 – PED data
GAHP-A HT STD
GAHP-A HT S1
PED data
COMPONENTS UNDER
PRESSURE
Generator
l
18,6
Leveling chamber
l
11,5
Evaporator
l
3,7
Cooling volume transformer
l
4,5
Cooling absorber solution
l
6,3
Solution pump
l
3,3
TEST PRESSURE (IN AIR)
bar g
55
MAXIMUM PRESSURE OF THE REFRIGERANT CIRCUIT
bar g
32
FILLING RATIO
kg of
NH3/l
0,146
FLUID GROUP
GROUP 1°
2 TRANSPORT AND POSITIONING
2�1 WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage
during appliance transport and installation.
On-site inspection
▶
Upon arrival at the site, ensure there is no transport
damage on packing, metal panels or finned coil.
▶
After removing the packing materials, ensure the ap-
pliance is intact and complete.
Packing
▶
Only remove the packing after placing the appliance
on site.
▶
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are
potentially dangerous.
Weight
▶
The crane and lifting equipment must be suitable for
the load.
▶
Do not stand under suspended loads.
2�2 HANDLING
Handling and lifting
▶
Always handle the appliance in its packing, as delivered by
the factory.
▶
To lift the appliance use straps or slings inserted in the holes
of the base (Figure 2.1 p. 19).
▶
Use lifting beams to avoid damaging the outer panels and
finned coil (Figure 2.1 p. 19).
▶
Comply with safety regulations at the installation site.