2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
6
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
Action at input error
(high)
[
-TIO-
, H-CIO-A]
WH
1
R/W
C
0: Normal control
1: Manipulated output value at
input error
0
a
Action at input error
(low)
[
-TIO-
, H-CIO-A]
WL
1
R/W
C
0: Normal control
1: Manipulated output value at
input error
0
AT bias
[
-TIO-
, H-CIO-A]
GB
6
R/W
C
Within
±
input span range
0
b
Setting change rate
limiter
[
-TIO-
, H-CIO-A]
HH
6
R/W
C
0.0 to 100.0 %/minutes of span
0.0
Output limiter high
[For Heat/Cool control:
Heat-side output limiter
(high)]
[
-TIO-
, H-CIO-A]
OH
6
R/W
C
Heat control, Position
proportioning control:
Output limiter low to 105.0 %
Heat/Cool control:
Heat-side output limiter (high):
−
5.0 % to
+
105.0 %
Heat-side output limiter (low):
−
5.0 % (fixed)
For details, refer to
Output
limiter
(P. 21)
.
100.0
Output limiter low
[For Heat/Cool control:
Cool-side output limiter
(high)]
[
-TIO-
, H-CIO-A]
OL
6
R/W
C
Heat control, Position
proportioning control:
−
5.0 % to Output limiter high
Heat/Cool control:
Cool-side output limiter (high):
−
5.0 % to
+
105.0 %
Cool-side output limiter (low):
−
5.0 % (fixed)
For details, refer to
Output
limiter (P. 21)
.
0.0
c
ON/OFF control
differential gap (upper)
[
-TIO-
, H-CIO-A]
IV
6
R/W
C
0.00 to 10.00
%
of span
0.02
a
Heat control (
-TIO-
/H-CIO-A): 0
Heat/Cool control (
-TIO-
/H-CIO-A): 1
Position proportioning control (H-TIO-K): 0
b
The position of the decimal point differs depending on the input range.
c
Heat control (
-TIO-
/H-CIO-A): 0.0
Heat/Cool control (
-TIO-
/H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 0.0