2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
20
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
PCP module
DI using selection
[H-PCP-B]
H4
6
R/W
U
0 to 7
a
Selection status is expressed as
a bit image in decimal number.
0
PCP module
DO de-energized
selection
[H-PCP-A,
M-PCP-A (Z-190)]
VS
6
R/W
U
0000 to 1111
b
0
★
Identifier that is only supported in the SR Mini HG SYSTEM.
a
Each DI selection status is assigned as a bit image in binary numbers. However, send data from the SR
Mini HG SYSTEM be changed to decimal ASCII code from the bit image in binary numbers.
Bit 7 ········ Bit 0
Bit image:
00000000
Calculation method of setting value:
Example: When DI1 to DI3 are used.
a
For the binary value, enter either 0 (unused) or 1 (used).
b
When calculating the setting, express the states for DI1 to DI3 as 1-digit binaries, then convert to
decimal.
c
The setting value is the sum of the calculation values for DI1 to DI3.
b
PCP module DO de-energized selection [H-PCP-A, M-PCP-A (Z-190) module]
DO4
DO3
DO2
DO1
0 0 0 0
7
COM
24 V DC
DI1
DI2
DI3
7
8
9
10
Converted to decima
b
Expressed
in binary
a
Value used for
calculation
1
×
1 (2
0
)
=
1
DI using selection setting value
c
1
×
2 (2
1
)
=
2
1
×
4 (2
2
)
=
4
+
Bit 0: DI1
Bit 1: DI2
Bit 2: DI3
Bit 3 to Bit 7: Unused
Bit data
0: Used 1: Unused
Data range
0: Energized
1: De-energized