2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
9
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
Temperature rise
completion hold function
[
-PCP-A/B]
EK
1
R/W
U
0: Not hold
1: Hold
1
Interval time setting
[
-PCP-A/B]
ZX
6
R/W
U
0 to 255 ms
0
Alarm 1 differential gap
[
-TIO-
, H-CIO-A]
HA
6
R/W
U
0.00 to 10.00
%
of span
0.10
Alarm 2 differential gap
[
-TIO-
, H-CIO-A]
HB
6
R/W
U
0.00 to 10.00
%
of span
0.10
Alarm 1 type selection
[
-TIO-
, H-CIO-A]
XA
1
R/W
U
0: Process high alarm
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
6: No alarm function
Depends on
model code
Alarm 2 type selection
[
-TIO-
, H-CIO-A]
XB
1
R/W
U
0: Process high alarm
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
6: No alarm function
Depends on
model code
Alarm 1 hold action
[
-TIO-
, H-CIO-A]
WA
1
R/W
U
0: Not provided
1: Provided
2: Re-hold action
Re-hold action will be valid in
deviation alarm.
Depends on
model code
Alarm 2 hold action
[
-TIO-
, H-CIO-A]
WB
1
R/W
U
0: Not provided
1: Provided
2: Re-hold action
Re-hold action will be valid in
deviation alarm.
Depends on
model code
Alarm 1 interlock
[
-TIO-
, H-CIO-A]
LA
1
R/W
U
0: Not provided
1: Provided
0
Alarm 2 interlock
[
-TIO-
, H-CIO-A]
LB
1
R/W
U
0: Not provided
1: Provided
0
Alarm 1 action at input
error
[
-TIO-
, H-CIO-A]
OA
1
R/W
U
0: Normal alarm action
1: Forced alarm ON when
temperature measured value
exceeds input error
determination point.
0
Continued on the next page.