2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
5
2.3 Extended Communication (Initialize Setting Mode)
Communication Data
Note that there are identifiers which indicate that communication is not possible depending
on the specification.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
Input range number
[
-TIO-
, H-CIO-A]
XI
6
R/W
C
-TIO-A/B/C/D/K/P: 0 to 63
H-TIO-E/F/G/R, H-CIO-A:
0 to 120
H-TIO-H/J:
0 to 12
If the input range number is
changed, all set values of the
corresponding module will be
changed (initialized).
Refer to
Input range table
(P. 30)
.
Depends on
model code
Setting limiter high
[
-TIO-
, H-CIO-A]
SH
6
R/W
C
TC/RTD input:
Setting limiter low to
Input range (high)
Input range
(high)
Voltage/Current input:
Setting limiter low to
Display scale high
Display scale
high
Setting limiter low
[
-TIO-
, H-CIO-A]
SL
6
R/W
C
TC/RTD input:
Input range (low) to
Setting limiter high
Input range
(low)
Voltage/Current input:
Display scale low to
Setting limiter high
Display scale
low
Digital filter
[
-TIO-
, H-CIO-A]
F1
6
R/W
C
-TIO-A/B/C/D/K/P:
0 to 100 seconds (0: OFF)
H-TIO-E/F/G/H/J/R, H-CIO-A:
0.0 to 100.0 seconds
(0.0: OFF)
0 or 0.0
Input error
determination point
(high)
[
-TIO-
, H-CIO-A]
AV
6
R/W
C
TC/RTD input:
Within input range
Input range
(high)
Voltage/Current input:
Within display scale range
Display scale
high
Input error
determination point
(low)
[
-TIO-
, H-CIO-A]
AW
6
R/W
C
TC/RTD input:
Within input range
Input range
(low)
Voltage/Current input:
Within display scale range
Display scale
low
Continued on the next page.