5. PREPARATION BEFORE OPERATION
IMSRM52-E4
30
3.
After completing the setting, engage the upper connection of the mainframe with that of the
mother block, then perform the reverse order of separation to engage the lower part of the
mainframe with the mother block with the upper connection set to the fulcrum. Firmly engage the
mainframe with the mother block until a click sound is produced.
The transmission speed that can be set differs depending on the total extension distance.
Maximum transmission
distance
Transmission
speed
Transmission speed setting
switch setting
1200 m
156 Kbps
0
900 m
625 Kbps
1
400 m
2.5 Mbps
2
160 m
5 Mbps
3
100 m
10 Mbps
4
5.3 Host Communication and Unit Address Settings
When host communication is made between the host computer and control unit, set the host computer
communication speed, data configuration and unit address. Set the communication speed and data
configuration using the dip switch in the H-PCP-G module. In addition, set the unit address using the
unit address setting switch at the front of the H-PCP-G module.
For details of the settings, see the separate
Communication Quick Manual
(IMS01V02-E )
.