background image

 
 
 
 
 
 

 
 

 

54  

IMSRM52-E4 

7.  EXAMPLES OF SEQUENCE 
 PROGRAMS 

This Chapter describes examples of sequence programs in the following system configuration. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Control & Communication Link system master/local unit (Master station) 

Station No.: 0 

Slot: 0 

 

SR Mini HG SYSTEM H-LNK-A module 

Station No.: 1 (4 stations occupied) 

 
System configuration used for examples of sequence programs 

 
 

The control unit (Temperature control unit) starts with control RUN/STOP transfer set 
to the control STOP state after power on. Set to control RUN on the PLC side after 
power on. 
However, if the initialize setting (Extended communication) Control RUN/STOP 
holding (0: Not holding prior to factory shipment) is changed to “1: Holding,” control 
starts while the state before STOP is being held.   
For details of the Control RUN/STOP holding settings, see the separate Supplementary 
Information for initialize settings (Extended Communication) (IMSRM07-E ).

 

 

When the control STOP state is changed to the control RUN state, set the setting flag 
after a delay time of about 5 seconds by using a timer for initialize processing in the 
temperature control unit. 

 
 

 

 

CPU unit

H-PCP-G

module 

H-LNK-A

module 

 

Master station 

Station 
No. 1

Station No. 0 
Slot 0 

SR Mini HG SYSTEM 

control unit 

(Temperature control unit)

Mitsubishi PLC 

Terminating 
resistor 

Station No. setting switch:

  Set to “1.” 

×

10 

×

Terminating 
resistor 

Содержание SR Mini HG SYSTEM H-LNK-A

Страница 1: ...SR Mini HG SYSTEM IMSRM52 E4 Power Supply CPU Module Link Module Control Communication Link H PCP G H LNK A Instruction Manual RKC INSTRUMENT INC...

Страница 2: ...STRUMENT INC The MELSEC and Control Communication Link system are products manufactured by Mitsubishi Electric Co Ltd Company names and product names used in this manual are the trademarks or register...

Страница 3: ...ed on to prevent electric shock fire or damage to instrument and equipment This instrument must be used in accordance with the specifications to prevent fire or damage to instrument and equipment This...

Страница 4: ...n each terminal screw to the specified torque found in the manual to avoid electric shock fire or malfunction For proper operation of this instrument provide adequate ventilation for heat dispensation...

Страница 5: ...1 H PCP G Module 10 2 2 H LNK A Module 13 3 MOUNTING 15 3 1 Mounting Environment 15 3 2 Dimensions 16 3 3 Mounting the Mother Block 18 3 4 Mounting the Module 20 3 5 Removing the Module 21 3 6 How to...

Страница 6: ...een Master Station and Remote Device Station 32 6 2 Remote Input Output 33 6 3 Remote Registers 43 6 4 Extension No 45 6 5 Flag Operation 51 7 EXAMPLES OF SEQUENCE PROGRAMS 54 7 1 List of Internal Rel...

Страница 7: ...the SR Mini HG SYSTEM consists of the dedicated power supply CPU module H PCP G the Link module H LNK A and temperature control function modules This manual describes the specifications mounting and...

Страница 8: ...nication Link system master local unit Mitsubishi Electric Co Ltd Confirmation of the products Confirmation of the model code See 1 3 Checking the Products P 3 See 1 4 Confirmation of the Model Code P...

Страница 9: ...module 1 module One H PCP H module power supply CPU module is required for each control unit H LNK A module Link module 1 module One H LNK A module Link module is required for one control unit Functio...

Страница 10: ...o function Alarm Code Table The selected function will be common for all the modules with alarm functions in the control unit H LNK A module Link module 1 Type A Control Communication Link connection...

Страница 11: ...connected to Control Communication Link Up to 16 units Up to 64 stations Up to 16 units When the host computer is connected Up to 16 units Only when RS 422A is SR Mini HG SYSTEM control unit Control...

Страница 12: ...function built in the temperature control modules H TIO A C D cannot be used Current transformer input module H CT A CT input 6 points type Each 2 points together are common For details of the temper...

Страница 13: ...cator lamp FAIL Red LED Turned off When the module is normal Turned on When the module is abnormal 5 Operation indicator lamp RUN Green LED Flashing The module operates normally 6 Modular connector 1...

Страница 14: ...setting error now occurs At intervals of 0 5 sec OFF for 0 25 sec ON for 0 25 sec 4 Operation indicator lamp RUN Green LED Turned on H LNK A module is not identified by H PCP G module or H LNK A modul...

Страница 15: ...munication terminals Control Communication Link connection terminals 7 Transmission speed setting switch Switch to set the transmission speed of the control unit and Control Communication Link master...

Страница 16: ...Control Communication Link connectable modules H TIO A B C D E F G H J P R H CT A H LNK A Number of temperature control channels Up to 16 channels control unit Number of connectable modules 8 modules...

Страница 17: ...ing Digital output can be selected from among the following outputs Temperature alarm First alarm Second alarm Heater break alarm HBA Burnout alarm Loop break alarm LBA Temp rise completion 5 Interfac...

Страница 18: ...ther the 1st alarm or 2nd alarm function when ordering The specified function is common to all of the modules with the alarm function within the control unit Temperature rise completion function Compl...

Страница 19: ...at the front of the module LED display RUN lamp Green LED Turned on H LNK A module is not identified by H PCP G module or H LNK A module is being initialized Flashing 1 The module operates normally A...

Страница 20: ...perature set value SV PID AT transfer Proportional band Heat side Proportional band Cool side Integral Time Derivative Time Control response designation parameters PV bias Communication items Remote r...

Страница 21: ...OLTAGE CATEGORY II POLLUTION DEGREE 2 2 Avoid the following conditions when selecting the mounting location Ambient temperature less than 0 C or more than 50 C Ambient humidity of less than 45 or more...

Страница 22: ...M52 E4 16 3 2 Dimensions External Dimensions 96 3 5 100 102 4 48 47 5 With the terminal cover fixed to the module Dotted line section Terminal cover Unit mm H PCP G module 96 100 23 5 24 9 3 5 Unit mm...

Страница 23: ...depth of each module is 108 mm from the mounting surface inside the panel to the module front with the module mounted on the DIN rails However when a connection cable modular connector is connected a...

Страница 24: ...G module Dimensions for closely connected mounting Unit mm 2 Remove the module from the mother block For details of removing the module see 3 5 Removing the Module P 21 3 Before fixing the mother bloc...

Страница 25: ...et of the mother block to the DIN rail and push the lower section into place on the DIN rail Figure 2 4 Slide the locking devices up to secure the mother block to the DIN rail Figure 3 5 Slide connect...

Страница 26: ...ach module Figure 1 3 2 Next insert the lower part of the module into the mother block centering around the section already inserted in item 1 Figure 2 4 Correctly clip the module main unit into the m...

Страница 27: ...ck press the bottom on the module lifting upward to release connection This figure shows the H LNK A module The H PCP G module can also be removed in the same way Press bottom of module and lift upwar...

Страница 28: ...ng a screw However when fixing the terminal over to the module using a screw use a 3 8 tapping round head screw taper thread As the screw is not attached to the module prepare it on the customer side...

Страница 29: ...sfactory noise filter effect select the most suitable type after due consideration of instrument power supply voltage and filter frequency characteristics To the instrument with power supply of 24 V p...

Страница 30: ...contact output 1a contact Open when abnormal Rating 250 V AC 0 1 A Resistive load When the FAIL condition occurs in any of the function modules in the control unit the FAIL output will also be output...

Страница 31: ...n the Model No label attached to the left side of the module as the Model No and code Check the description and then conduct the wiring accordingly Relay contact output 1a contact Closed at alarm occu...

Страница 32: ...icated to Control Communication Link Ver 1 10 Ground both ends of the shield wire on the twisted pair cable so that the grounding resistance is 100 or less via the SLD or FG terminal of each module In...

Страница 33: ...g torque Recommended value 0 4 N m 4 kgf cm H LNK A module Communication terminals Mitsubishi PLC SR Mini HG SYSTEM control unit SR Mini HG SYSTEM control unit Control Communication Link dedicated cab...

Страница 34: ...mping of 4 stations Setting example Head Head Station No 1 Station No 2 Station No 3 Station No 4 Station No 5 Station No 6 Station No 7 Station No 8 Station No 9 16 temperature control channels every...

Страница 35: ...the same line Otherwise a normal data link cannot be made Setting procedure 1 To separate the module mainframe from the mother block press the bottom on the module lifting upward to release connectio...

Страница 36: ...distance Maximum transmission distance Transmission speed Transmission speed setting switch setting 1200 m 156 Kbps 0 900 m 625 Kbps 1 400 m 2 5 Mbps 2 160 m 5 Mbps 3 100 m 10 Mbps 4 5 3 Host Communic...

Страница 37: ...ontrol Communication Link is not normally connected after the power to the control unit is turned on As control start RUN cannot be set on the PLC side control continues to stop STOP The control unit...

Страница 38: ...Write the data in the remote register RWw using the TO instruction 8 The data is stored in the remote register RWw of the remote device station Temperature control unit by link scanning 9 The remote r...

Страница 39: ...f remote input 4 stations occupied Temperature control 16 channels Direction Remote device station Temperature control unit Master station PLC Address Details RXn0 CH1 First alarm status OFF Alarm OFF...

Страница 40: ...Heater break alarm HBA status OFF Alarm OFF ON Alarm ON RX n 2 4 CH3 PID AT transfer status OFF PID control ON AT Autotuning RX n 2 5 CH4 First alarm status OFF Alarm OFF ON Alarm ON RX n 2 6 CH4 Sec...

Страница 41: ...BA status OFF Alarm OFF ON Alarm ON RX n 3 D CH8 PID AT transfer status OFF PID control ON AT Autotuning RX n 3 E Unused RX n 3 F Unused RX n 4 0 CH9 First alarm status OFF Alarm OFF ON Alarm ON RX n...

Страница 42: ...H14 Second alarm status OFF Alarm OFF ON Alarm ON RX n 5 B CH14 Burnout alarm status OFF Alarm OFF ON Alarm ON RX n 5 C CH14 Heater break alarm HBA status OFF Alarm OFF ON Alarm ON RX n 5 D CH14 PID A...

Страница 43: ...7 0 Reserved RX n 7 1 Reserved RX n 7 2 Reserved RX n 7 3 Reserved RX n 7 4 Reserved RX n 7 5 Reserved RX n 7 6 Reserved RX n 7 7 Reserved RX n 7 8 Initialize data processing request flag RX n 7 9 In...

Страница 44: ...any one of 0 to 63 by RYn6 to RYnB b0 to b5 ON OFF RYn9 b3 For details of 0 to 63 see 6 4 Extension No P 45 RYnA b4 RYnB b5 RYnC Extended display flag 1 RYnD Extended setting flag 1 RYnE Unused RYnF C...

Страница 45: ...4 Unused RY n 1 5 Unused RY n 1 6 Unused RY n 1 7 Unused RY n 1 8 Unused RY n 1 9 Unused RY n 1 A Unused RY n 1 B Unused RY n 1 C Unused RY n 1 D Unused RY n 1 E Unused RY n 1 F Unused RY n 2 0 Unused...

Страница 46: ...4 Unused RY n 3 5 Unused RY n 3 6 Unused RY n 3 7 Unused RY n 3 8 Unused RY n 3 9 Unused RY n 3 A Unused RY n 3 B Unused RY n 3 C Unused RY n 3 D Unused RY n 3 E Unused RY n 3 F Unused RY n 4 0 Unused...

Страница 47: ...4 Unused RY n 5 5 Unused RY n 5 6 Unused RY n 5 7 Unused RY n 5 8 Unused RY n 5 9 Unused RY n 5 A Unused RY n 5 B Unused RY n 5 C Unused RY n 5 D Unused RY n 5 E Unused RY n 5 F Unused RY n 6 0 Unused...

Страница 48: ...7 0 Reserved RY n 7 1 Reserved RY n 7 2 Reserved RY n 7 3 Reserved RY n 7 4 Reserved RY n 7 5 Reserved RY n 7 6 Reserved RY n 7 7 Reserved RY n 7 8 Initialize data processing completion flag RY n 7 9...

Страница 49: ...1 or 5 For station No 1 Remote register RWrn to RWrn F RWr0 to RWrF RWwm to RWwm F RWw0 to RWwF For station No 5 Remote register RWrn to RWrn F RWr10 to RWr1F RWwm to RWwm F RWw10 to RWw1F List of rem...

Страница 50: ...nB is processed Example When Extension No for display is set to 1 or Extension No for setting is set to 9 Extension No for display Set to 1 RYn5 RYn4 RYn3 RYn2 RYn1 RYn0 OFF OFF OFF OFF OFF ON Remote...

Страница 51: ...range Displays the temperature measured value 1 Manipulated output Heat side RO 5 0 to 105 0 Displays the manipulated output on the heat side 2 CT input measured value RO 0 0 to 30 0 A CTL 6 type 0 0...

Страница 52: ...pending on the specification 11 Cannot be used 12 Cannot be used 13 Cannot be used 14 Cannot be used 15 Cannot be used 16 Cannot be used 17 Control RUN STOP status RO 0 Control stop 1 Control run Disp...

Страница 53: ...value and alarm set value 26 Manipulated output Cool side RO 5 0 to 105 0 Displays the manipulated output on the cool side 27 Proportional band Cool side R W 0 1 to 1000 0 of span Sets the proportion...

Страница 54: ...Error code RO For details of the data see page 50 Displays the error code during system error occurrence at operation or power on Only RWrn data is effective 33 Memory area number R W 1 to 8 Changes...

Страница 55: ...arm LBA 49 Loop break alarm LBA use selection R W 0 Unused 1 Used Sets use unuse of the control loop break alarm LBA 0 50 LBA time setting R W 1 to 7200 seconds Sets the loop break alarm LBA time 480...

Страница 56: ...r input measured value read from the CT is smaller than the preset heater break alarm set value even with the control output produced the heater break alarm is turned on Welding detection If the curre...

Страница 57: ...t flag RX n 7 8 is turned on Thus turn on the initialize data processing completion flag RY n 7 8 Initialize processing request from master station PLC This is an SR Mini HG initialize setting request...

Страница 58: ...to clear the error code Extension No for display selection processing The content of the extended display remote register is selected Error status flag RX n 7 A Error reset request flag RY n 7 A Remot...

Страница 59: ...conds are required to update data items such as set values SV and PID constants Read the above data items after a lapse of more than two seconds Extension No for setting RYn6 to RYnB Extended setting...

Страница 60: ...Extended communication Control RUN STOP holding 0 Not holding prior to factory shipment is changed to 1 Holding control starts while the state before STOP is being held For details of the Control RUN...

Страница 61: ...xtension No for display RYn2 M14 b3 RYn3 M15 b4 RYn4 M16 b5 RYn5 M17 b0 RYn6 M18 b1 RYn7 M19 b2 Extension No for setting RYn8 M20 b3 RYn9 M21 b4 RYnA M22 b5 RYnB M23 Extended display flag RYnC M24 Ext...

Страница 62: ...D M45 Work area RY n 7 E M46 Work area RY n 7 F M47 M48 Unused M49 M50 M51 CH1 First alarm status RXn0 M52 CH1 Second alarm status RXn1 M53 CH1 Burnout alarm status RXn2 M54 CH1 Heater break alarm HB...

Страница 63: ...rk area RX n 7 3 M75 Work area RX n 7 4 M76 Work area RX n 7 5 M77 Work area RX n 7 6 M78 Work area RX n 7 7 M79 Initialize data processing request flag RX n 7 8 M80 Initialize data setting completion...

Страница 64: ...erature measured value PV D25 CH5 Temperature measured value PV D26 CH6 Temperature measured value PV D27 CH7 Temperature measured value PV D28 CH8 Temperature measured value PV D29 CH9 Temperature me...

Страница 65: ...value SV D52 CH12 Temperature set value SV D53 CH13 Temperature set value SV D54 CH14 Temperature set value SV D55 CH15 Temperature set value SV D56 CH16 Temperature set value SV D57 CH1 Set value ch...

Страница 66: ...ation Reserved station specification 0 No reservation made Number of automatic recovery stations 1 station Number of retries 3 times Number of connected stations 1 station MOVK1 D0 MOVK3 D1 MOVK D2 M1...

Страница 67: ...ad of alarm state data etc from SR Mini HG in M relay 16 channels SR Mini HG SYSTEM control unit initialize M39 Initialize data processing completion flag M40 Initialize data setting request flag M41...

Страница 68: ...using a timer for initialize processing in the temperature control unit Temperature set value SV CH1 150 Temperature set value SV CH2 100 Data transfer Setting extension No setting Extension No 3 Set...

Страница 69: ...te Data range Factory set value Control Communication Link Selecting flag C2 1 RO 0 Selecting not provided 1 Selecting provided Attributes RO Read only Description of function Read only identifier whi...

Страница 70: ...Write Description of function Identifier which defines the remote register channel specification No of channels occupied in Control Communication Link If you need the Supplementary Information Initial...

Страница 71: ...xample If the station No of the H LNK A module is 1 or 5 For station No 1 Remote register RWrn to RWrn F RWr0 to RWrF RWwm to RWwm F RWw0 to RWwF For station No 5 Remote register RWrn to RWrn F RWr10...

Страница 72: ...wm 8 to RWwm F is ignored RWwm E CH7 RWwm F CH8 Data on the Extension No specified by the remote output RYn0 to RYn5 or RYn6 to RYnB is processed Example When Extension No for display is set to 1 or E...

Страница 73: ...The 1st edition MAR 1998 The 4th edition MAY 2006 IMQ00...

Страница 74: ...IMSRM52 E4 MAY 2006 RKC INSTRUMENT INC HEADQUARTERS 16 6 KUGAHARA 5 CHOME OHTA KU TOKYO 146 8515 JAPAN PHONE 03 3751 9799 81 3 3751 9799 E mail info rkcinst co jp FAX 03 3751 8585 81 3 3751 8585...

Отзывы: