6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E4
35
Continued from the previous page.
Direction: Remote device station (Temperature control unit)
→
Master station (PLC)
[Remote input]
Address Details
RX(n+3)0
CH6 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)1
CH6
Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)2
CH6
Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)3
CH6
PID/AT transfer status (OFF: PID control, ON: AT
<
Autotuning
>
)
RX(n+3)4
CH7
First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)5
CH7 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)6
CH7
Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)7
CH7
Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)8
CH7
PID/AT transfer status (OFF: PID control, ON: AT
<
Autotuning
>
)
RX(n+3)9
CH8
First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)A
CH8 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)B
CH8
Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)C
CH8
Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)D
CH8
PID/AT transfer status (OFF: PID control, ON: AT
<
Autotuning
>
)
RX(n+3)E
Unused
RX(n+3)F
Unused
RX(n+4)0
CH9
First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)1
CH9 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)2
CH9
Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)3
CH9
Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)4
CH9
PID/AT transfer status (OFF: PID control, ON: AT
<
Autotuning
>
)
RX(n+4)5
CH10
First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)6
CH10 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)7
CH10
Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)8
CH10
Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)9
CH10
PID/AT transfer status (OFF: PID control, ON: AT
<
Autotuning
>
)
RX(n+4)A
CH11
First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)B
CH11 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)C
CH11
Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)D
CH11
Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)E
CH11
PID/AT transfer status (OFF: PID control, ON: AT
<
Autotuning
>
)
RX(n+4)F
CH12
First alarm status (OFF: Alarm OFF, ON: Alarm ON)
Continued on the next page.