3. MOUNTING
This Chapter describes the mounting procedures for the H-PCP-G and H-LNK-A modules. For details
of the mounting procedures for other modules and the mounting position of the control unit, see the
Hardware Quick manual (IMS01V01-E )
.
Mount the H-PCP-G module on the left side of the control unit.
In order to facilitate the wiring and connection of the H-LNK-A module, the module
should be mounted on the right side of the control unit.
3.1 Mounting Environment
(1) This instrument is intended to be used under the following environmental conditions. (
IEC61010-1
)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Avoid the following conditions when selecting the mounting location:
•
Ambient temperature less than 0 °C or more than 50 °C.
•
Ambient humidity of less than 45 % or more than 85 % RH.
(Absolute humidity: MAX. W. C 29 g/m
3
dry air at 101.3 kPa)
•
Rapid changes in ambient temperature which may cause condensation.
•
Corrosive or inflammable gases.
•
Direct vibration or shock to the mainframe.
•
Water, oil, chemicals, vapor or steam splashes.
•
Excessive dust, salt or iron particles.
•
Excessive induction noise, static electricity, magnetic fields or noise.
•
Direct air flow from an air conditioner.
•
Exposure to direct sunlight.
•
Excessive heat accumulation.
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
WARNING
!