116
Connection
Description
Input
En
A 0 to 1 transition at En (Enable) triggers the output of the
message text.
Input
P
P is the priority of the message text.
1 is the lowest, 32 is the highest priority.
Quit: Acknowledgement of the message text
Parameter
Text:
Input of the message text
Par:
Parameter or actual value of another, already configured
function (see "Visible parameters or actual values")
Time:
Shows the continuously updated time-of-day
Date:
Shows the continuously updated date
EnTime:
Shows the time of the 0 to 1 transition
EnDate:
Shows the 0 to 1 transition of the date
Output
Q
Q remains set as long as the message text is queued.
Description of the function
With a 0 to 1 transition of the signal at input En, the display outputs your configured message text (actual
value, text, TOD, date) in RUN mode.
Acknowledgement disabled (Ack = Off):
The message text is hidden with a 0 to 1 signal transition at input En.
Acknowledgement enabled (Ack = On):
After input En is reset to 0, the message text is displayed until acknowledged by pressing the OK button.
The message text cannot be acknowledged as long as input En is high.
If several message text functions were triggered with En=1, the message with the highest priority (1 =
lowest, 64=highest) is displayed. This also implies that a new message text is only displayed if its priority
is higher than that of previously enabled message texts.
After a message text is disabled or acknowledged, the function automatically shows the previously active
message text that takes the highest priority.
You can press the and
keys to step through multiple active message texts.
Example
This is how two message texts could be shown:
Display field of xLogic in RUN mode
Содержание ELC-12AC-R-N
Страница 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Страница 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Страница 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Страница 40: ...40...
Страница 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Страница 121: ...121 E F digital flag status F AF analog flag value...
Страница 122: ...122 G M status H AM value...
Страница 221: ...221 7 Click Install button to install Program is being installed...
Страница 247: ...247 Right click Q2 and then click Set Output State Click OK button and the Q2 of xLogic will be turned off...
Страница 250: ...250...
Страница 256: ...256 You can read the parameters from the PLC...
Страница 258: ...258...
Страница 264: ...264 Our xLogicApp Smart phone is tcp client Interface configure Modbus Poll works as TCP client...
Страница 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Страница 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Страница 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Страница 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Страница 291: ...291 Slave3 IP 192 168 0 103 TCP server port 8003 Step 2 Program in master and slave Master program...
Страница 292: ...292 B001 is used to write I1 status to F1 of slave1 the Remote 1 is the target1 in the network parameter settings...
Страница 293: ...293 B002 is used to write I1 status to F1 of slave1 the Remote 2 is the target2 in the network parameter settings...
Страница 305: ...305 Slave3 IP 192 168 0 103 UDP Server port 8003 Step 2 Program in master and slave Master program...
Страница 317: ...317 Network settings You can view the network parameters in such table...
Страница 328: ...328 Program in master You need use the MODBUS BLOCK to realize the data transmission between master and slaves...
Страница 329: ...329 B001 Transfer the I1 IA status from the master to the Q1 QA of the slave1 Setting as follows...
Страница 330: ...330 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Страница 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Страница 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Страница 350: ...350 Components S1 S4 make contact Momentary switch B1 make contact Daylight control switch Circuit diagram by xLogicsoft...
Страница 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Страница 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Страница 392: ...392...