198
ELC-12AC-R-N
ELC-22DC-DA-R-N
ELC-22AC-R-N
Connection
Description
Trg
If there is a trigger at the Trg pin, then the Ethernet modem will be
reset , The modem will be startup again until the time "Reset period"
reached.
Parameter
Channel: Ethernet
Reset period:1—100s
Output
When the Ethernet module had been reset successfully, this block will
output a short trigger.
Description of the function
In order to monitor the communication status of the Ethernet to see if it is normal or continuous(or avoid
the Ethernet module is dead by unknown cause), sometimes we need reset the Ethernet module built-in
in the CPU when the communication has failed or been timeout.
Just one parameter to be set is the "Reset period" as follows:
Here are two examples with detailed description on how to use these blocks in the program.
Example 1
Just as below program shows, after the CPU running, we can push down the digital input1(just need a
short trigger to reset the Ethernet modem), after the Reset period(here is 5s) is reached, the Ethernet
modem will start up and this block will output a short trigger at the same time.
Example2
We also can use such “device reset” block along with the “Com status” function block together in the
program, when there is no data transmission through the Ethernet port while the timeout period(50s) is
reached, the com port status will output HI signal ,and then the Device reset block would be enabled and
the Ethernet module will be reset for the Reset period in the device reset block property dialog box.
Содержание ELC-12AC-R-N
Страница 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Страница 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Страница 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Страница 40: ...40...
Страница 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Страница 121: ...121 E F digital flag status F AF analog flag value...
Страница 122: ...122 G M status H AM value...
Страница 221: ...221 7 Click Install button to install Program is being installed...
Страница 247: ...247 Right click Q2 and then click Set Output State Click OK button and the Q2 of xLogic will be turned off...
Страница 250: ...250...
Страница 256: ...256 You can read the parameters from the PLC...
Страница 258: ...258...
Страница 264: ...264 Our xLogicApp Smart phone is tcp client Interface configure Modbus Poll works as TCP client...
Страница 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Страница 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Страница 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Страница 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Страница 291: ...291 Slave3 IP 192 168 0 103 TCP server port 8003 Step 2 Program in master and slave Master program...
Страница 292: ...292 B001 is used to write I1 status to F1 of slave1 the Remote 1 is the target1 in the network parameter settings...
Страница 293: ...293 B002 is used to write I1 status to F1 of slave1 the Remote 2 is the target2 in the network parameter settings...
Страница 305: ...305 Slave3 IP 192 168 0 103 UDP Server port 8003 Step 2 Program in master and slave Master program...
Страница 317: ...317 Network settings You can view the network parameters in such table...
Страница 328: ...328 Program in master You need use the MODBUS BLOCK to realize the data transmission between master and slaves...
Страница 329: ...329 B001 Transfer the I1 IA status from the master to the Q1 QA of the slave1 Setting as follows...
Страница 330: ...330 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Страница 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Страница 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Страница 350: ...350 Components S1 S4 make contact Momentary switch B1 make contact Daylight control switch Circuit diagram by xLogicsoft...
Страница 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Страница 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Страница 392: ...392...