PROBLEM
POSSIBLE CAUSE
SOLUTION
THE BUZZER SOUNDS
CONTINUOUSLY AND
THE DISPLAY SHOWS
ONE OF THE FOLLOWING
CODES:
A54, F50, F51,
F52, L50, L51, L52
THE LOAD APPLIED TO
THE UPS IS TOO HIGH
Reduce the load to within the threshold of 100% (or user
threshold in the case of code
A54
).
If the display shows a lock, remove the load and switch
the UPS off and back on again.
THE DISPLAY SHOWS
THE FOLLOW CODE:
A61
REPLACE THE BATTERIES Contact the support centre for battery replacement.
THE DISPLAY SHOWS
THE FOLLOW CODE:
A62
BATTERY MISSING OR NOT
CONNECTED
Check that the battery pack is present and connected
THE DISPLAY SHOWS
THE FOLLOW CODE:
A63
THE BATTERIES ARE FLAT;
THE UPS IS WAITING FOR
THE BATTERY VOLTAGE
TO EXCEED THE SET
THRESHOLD
Wait until the batteries have recharged or force power-
on manually by holding down the “ON” button for at least
2 seconds.
THE BUZZER SOUNDS
CONTINUOUSLY AND
THE DISPLAY SHOWS
THE FOLLOW CODE:
F38
THE UPS IS
MALFUNCTIONING; IT WILL
PROBABLY LOCK SOON
If possible, disconnect the power to the load, switch the
UPS off and back on again; if the problem occurs again,
call the support centre.
THE BUZZER SOUNDS
CONTINUOUSLY AND
THE DISPLAY SHOWS
ONE OF THE FOLLOWING
CODES:
F04, L04
THE TEMPERATURE OF
THE HEATSINKS INSIDE
THE UPS IS TOO HIGH
Check that the temperature of the environment in which
the UPS is located does not exceed 40°C.
THE BUZZER SOUNDS
CONTINUOUSLY AND
THE DISPLAY SHOWS
ONE OF THE FOLLOWING
CODES:
F53, L53
THERE IS A FAULT ON ONE
OR MORE OF THE
UTILITIES POWERED BY
THE UPS
Disconnect all the utilities, switch the UPS off and back
on again, reconnect the utilities one at a time to identify
which one is faulty.
THE BUZZER SOUNDS
CONTINUOUSLY AND
THE DISPLAY SHOWS
ONE OF THE FOLLOWING
CODES:
F60, L05, L07,
L13, L20, L21, L40, L41,
L42, L43
THE UPS IS
MALFUNCTIONING
If possible, disconnect the power to the load, switch the
UPS off and back on again; if the problem occurs again,
call the support centre.
THE DISPLAY SHOWS
ONE OF THE FOLLOWING
CODES:
C01, C02, C03
A REMOTE COMMAND IS
ACTIVE
If unwanted, check the status of the command inputs on
any optional contact card.
THE DISPLAY SHOWS
C02
THE “BATTERY SWAP”
MODE IS ACTIVATED”
To exit from the “battery swap” mode, press and hold the
ON/SEL buttons for at least 4 seconds
ATTENTION:
The UPS in case of a permanent failure will be not able to supply the load. To ensure total protection of
your equipment we suggest you install an ATS device (Automatic Transfer Switch) or an external automatic
by-pass.