14
UPS
CONFIGURATION
The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for
individual requirements. It is possible to perform these operations using the
UPStools
software.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Output frequency
Selects the nominal output
frequency
Auto
•
50 Hz
•
60 Hz
•
Auto: automatic learning of the input frequency
Output voltage
Selects the nominal output
voltage
230V
220 - 240 in 1V steps
Operating mode
Select one of the available
operating modes
L.I.
•
L.I.
•
ECO
•
OTHER (MODE)
Power-off due to
minimum charge
Automatic UPS power-off in
battery operation mode if
the charge is lower than 5%
Disabled
•
Enabled
•
Disabled
Autonomy limit
Maximum battery operation
time
Disabled
•
Disabled (complete battery discharge)
•
(1 - 65000) sec. in 1 sec steps
Battery low
warning
Estimated autonomy time
remaining for the battery
low warning
3 min.
(1 - 255) min. in 1 min steps
Battery test
Interval of time for the
automatic battery test
40 hours
•
Disabled
•
(1 - 1000) h in 1 hour steps
Maximum charge
alarm threshold
Selects the user overcharge
limit
Disabled
•
Disabled
•
(0 - 103) % in 1% steps
EnergyShare
Select the auxiliary socket
operating mode
Always
connected
•
Always connected
•
Disconnection after no. seconds of battery
operation
•
Disconnection after no. seconds of the battery
discharge pre-alarm signal
•
... (see
UPStools
manual)
Input frequency
tolerance range
Select the required input
frequency range for normal
operation
± 5%
(±3 - ±10) % in 1% steps
Power-on delay
Waiting time for automatic
switching back on after
mains power returns
5 sec.
•
Disabled
•
(1 - 255) sec. in 1 sec steps
Remote power-
on/off function
Selects the function
associated with the RS232
connector.
Disabled
•
Disabled
•
Remote ON
•
Remote OFF
•
Remote ON/OFF