background image

 

 

 

USE 

 

C

ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME

 

1)  Confirm that the installation upstream of the UPS is adequately protected against overloads and short circuits. It 

is recommended that the rating of this protection is either 10A or 16A type B or C (depending on the UPS power 
rating), always check prior to connection. 

2)  Power the UPS using the input cable provided. 

3)  Press the ON/OFF switch located on the front panel. 

4)  After a few moments, the UPS will switch on, the display will light up, there will be a beep and the 

 icon will 

start to flash. The UPS is in stand-by mode: meaning that it is only consuming a small amount of power. The 
microcontroller supervising the self-diagnoses is powered; the batteries are charging; and everything is ready 
for UPS activation. Battery operation is also in stand-by mode provided that the timer is active. 

5)  Ensure that the cables connecting any devices to the output sockets of the UPS do not exceed a maximum of 

10m in length. 

6)  Check which operating mode is set on the display and, if necessary, see the “

Configuring operating modes

” 

paragraph to set the required mode. For advanced UPS configurations execute the software UPSTools which 
can be downloaded from the web site 

www.riello-ups.com.

 

 
 
 

S

WITCHING ON FROM THE MAINS

 

1)  Press the “ON” button for 1 second. After pressing it, all the icons on the display light up for 1 second and the 

UPS beeps. 

2)  Switch on the equipment connected to the UPS. 

When switching on for the first time only:

 after 30 seconds, check that the UPS is operating correctly: 

1)  Simulate a blackout by disconnecting power to the UPS. 

2)  The load must continue to be powered, the 

 icon on the display must light up and there must be a beep 

every 4 seconds. 

3)  When power is reconnected, the UPS must go back to operating from the mains. 

 
 
 

S

WITCHING ON FROM THE BATTERY

 

1)  Press the ON/OFF switch located on the front panel. 

2)  Hold down the “ON” button for at least 5 seconds. All the icons on the display light up for 1 second. 

3)  Switch on the equipment connected to the UPS. 

 
 
 

S

WITCHING OFF THE 

UPS 

In order to switch off the UPS, hold down the “STBY” button for at least 2 seconds. The UPS goes back to stand-by 

mode and the 

 icon starts to flash: 

1)  If the mains power is present, the ON/OFF switch must be pressed to completely turn off the UPS. 

2)  During battery mode operation with the timer not set, the UPS automatically switches off after 30 seconds. 

However if, the timer is set, press and hold down the "STBY" key for at least 5 seconds to turn off the UPS. For 
complete shutdown, press the ON/OFF switch. 

 

 

Содержание VST 1100

Страница 1: ......

Страница 2: ...the environmental aspects All our products pursue the objectives defined in the environmental management system developed by the company in compliance with applicable standards No hazardous materials...

Страница 3: ...OM THE BATTERY 9 SWITCHING OFF THE UPS 9 DISPLAY PANEL MESSAGES 10 UPS STATUS MESSAGES 10 MEASUREMENT DISPLAY AREA 11 CONFIGURING THE OPERATING MODE 12 POSSIBLE SETTINGS 12 ADDITIONAL FUNCTIONS 12 SOF...

Страница 4: ...system available for network devices servers and conventional storage systems The VISION series is a range of UPS which utilises the very latest Line Interactive technology and sinusoidal output volt...

Страница 5: ...5 UPS VIEWS FRONT VIEW Display Removable front panel Multipurpose buttons Battery pack connector ON OFF Switch Battery pack retention panel...

Страница 6: ...EAR VIEW 800VA 1100VA Model 1500VA 2000VA Model Communication port RS232 Cooling fans USB communication port IEC 10A output socket Circuit breaker Energyshare Communication Card Slots IEC 10A input pl...

Страница 7: ...ect Load level indicator ON button Configuration area STAND BY button Maintenance request Regular operation Timer Mains operation Measurement display area Battery operation Stand by alarm AVR active E...

Страница 8: ...m bad weather The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table The ambient temperature whilst the UPS is in operation must remain between 0...

Страница 9: ...s which can be downloaded from the web site www riello ups com SWITCHING ON FROM THE MAINS 1 Press the ON button for 1 second After pressing it all the icons on the display light up for 1 second and t...

Страница 10: ...tage charge of the batteries Dynamic Indicates the percentage of charge applied to the UPS compared with the nominal value Flashing Maintenance is required Contact the support centre Fixed Indicates t...

Страница 11: ...examples are shown below GRAPHIC EXAMPLE 1 DESCRIPTION GRAPHIC EXAMPLE 1 DESCRIPTION Mains voltage Battery charge percentage Mains frequency Total battery voltage UPS output voltage Applied load perce...

Страница 12: ...switched on the load is disconnected in the event of a mains blackout If the input mains deviates from the established tolerances the UPS automatically switches to Stdby mode and disconnects the load...

Страница 13: ...full display of the status of the UPS via USB or RS232 For a list of possible configurations available to the user refer to the UPS Configuration paragraph INSTALLATION OPERATIONS 1 Connect one of the...

Страница 14: ...attery discharge 1 65000 sec in 1 sec steps Battery low warning Estimated autonomy time remaining for the battery low warning 3 min 1 255 min in 1 min steps Battery test Interval of time for the autom...

Страница 15: ...UPS refer to the manual provided 2 TXD 3 RXD 4 Programmable input default disabled 5 GND 6 Power supply DC Imax 20mA 7 Programmable input default disabled 8 Programmable output default low battery pr...

Страница 16: ...INS FAILURE THE BATTERY PACK IS VERY HEAVY USE EXTREME CAUTION WHEN REPLACING IT 1 Set the UPS in battery swap mode by pressing and holding both the ON and SEL button for 4 seconds See par USE Operati...

Страница 17: ...in the same number and type of batteries see the label located on the battery pack near the connector 5 Insert the new battery pack into the compartment sliding it into the UPS Replace the battery pac...

Страница 18: ...IS NOT POWERED THE UPS IS IN STAND BY MODE Press the ON button on the front panel to power the loads NO CONNECTION TO THE LOAD Check the connection to the load THE UPS IS OPERATING FROM THE BATTERY DE...

Страница 19: ...HOWS ONE OF THE FOLLOWING CODES F04 L04 THE TEMPERATURE OF THE HEATSINKS INSIDE THE UPS IS TOO HIGH Check that the temperature of the environment in which the UPS is located does not exceed 40 C THE B...

Страница 20: ...mance or prevent certain functions from being used CODE DESCRIPTION A06 Sensor1 temperature under 0 C A08 Sensor2 temperature under 0 C A54 Load percentage greater than the user threshold set A61 Repl...

Страница 21: ...he load being powered by the bypass line this procedure is excluded for locks due to serious persistent overloads and short circuits CODE DESCRIPTION L04 Heatsink over temperature L05 Temperature sens...

Страница 22: ...ing 110 load 150 From mains locked after 10 sec From battery locked after 5 sec Load overload 150 From mains locked after 1 sec From battery locked 0 5 sec OTHER DATA Leakage current towards ground mA...

Страница 23: ...0MNVST800RUENUA...