TROUBLESHOOTING 

Irregular UPS operation is not always an indication of a fault, and can be due to minor or easy-to-resolve issues  
It is therefore advisable to consult the table below as it contains information which is useful for solving the most common 
UPS problems. 
 
 

PROBLEM 

POSSIBLE CAUSE 

SOLUTION 

 

THE DISPLAY DOES NOT 

LIGHT UP 

ON/OFF SWITCH NOT 

PRESSED 

Press the ON/OFF switch on the front panel. 

MAIN CONNECTION CABLE 

MISSING 

Check that the power cable is connected correctly. 

NO MAINS VOLTAGE 

(BLACKOUT) 

Check that the power reaches the socket where the UPS 
is connected (try it with a table lamp, for example). 

INTERVENTION OF THE 

INPUT CIRCUIT BREAKER 

If present, reset the circuit breaker by pressing the 
button on the back of the UPS. 
CAUTION: Check that there is no output overload to the 
UPS. 

 

THE DISPLAY IS ON BUT 

THE LOAD IS NOT 

POWERED 

THE UPS IS IN STAND-BY 

MODE 

Press the “ON” button on the front panel to power the 
loads. 

NO CONNECTION TO THE 

LOAD 

Check the connection to the load. 

 

THE UPS IS OPERATING 

FROM THE BATTERY 

DESPITE THE PRESENCE 

OF MAINS VOLTAGE 

THE INPUT VOLTAGE IS 

OUTSIDE THE PERMITTED 

TOLERANCE RANGE FOR 

MAINS OPERATION  

Problem with the mains. Wait until the input mains 
voltage returns within the tolerance range. The UPS will 
automatically return to mains operation.  

INTERVENTION OF THE 

INPUT CIRCUIT BREAKER 

If present, reset the circuit breaker by pressing the 
button on the back of the UPS. 
CAUTION: Check that there is no output overload to the 
UPS. 

 

THE UPS DOES NOT 

COME ON AND THE 

DISPLAY SHOWS THE 

CODE: 

A06, A08

 

THE TEMPERATURE OF 

THE UPS IS LOWER THAN 

0°C  

Check the temperature of the environment in which the 
UPS is located; if it is too low, bring it past the minimum 
threshold (0°C). 

 

THE DISPLAY SHOWS 
THE FOLLOW CODES: 

L11

 

INPUT RELAY FAULTY 

Switch off and disconnect the UPS from the power 
supply and contact the support centre. 

 

 
 

 

 

Содержание VST 1100

Страница 1: ......

Страница 2: ...the environmental aspects All our products pursue the objectives defined in the environmental management system developed by the company in compliance with applicable standards No hazardous materials...

Страница 3: ...OM THE BATTERY 9 SWITCHING OFF THE UPS 9 DISPLAY PANEL MESSAGES 10 UPS STATUS MESSAGES 10 MEASUREMENT DISPLAY AREA 11 CONFIGURING THE OPERATING MODE 12 POSSIBLE SETTINGS 12 ADDITIONAL FUNCTIONS 12 SOF...

Страница 4: ...system available for network devices servers and conventional storage systems The VISION series is a range of UPS which utilises the very latest Line Interactive technology and sinusoidal output volt...

Страница 5: ...5 UPS VIEWS FRONT VIEW Display Removable front panel Multipurpose buttons Battery pack connector ON OFF Switch Battery pack retention panel...

Страница 6: ...EAR VIEW 800VA 1100VA Model 1500VA 2000VA Model Communication port RS232 Cooling fans USB communication port IEC 10A output socket Circuit breaker Energyshare Communication Card Slots IEC 10A input pl...

Страница 7: ...ect Load level indicator ON button Configuration area STAND BY button Maintenance request Regular operation Timer Mains operation Measurement display area Battery operation Stand by alarm AVR active E...

Страница 8: ...m bad weather The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table The ambient temperature whilst the UPS is in operation must remain between 0...

Страница 9: ...s which can be downloaded from the web site www riello ups com SWITCHING ON FROM THE MAINS 1 Press the ON button for 1 second After pressing it all the icons on the display light up for 1 second and t...

Страница 10: ...tage charge of the batteries Dynamic Indicates the percentage of charge applied to the UPS compared with the nominal value Flashing Maintenance is required Contact the support centre Fixed Indicates t...

Страница 11: ...examples are shown below GRAPHIC EXAMPLE 1 DESCRIPTION GRAPHIC EXAMPLE 1 DESCRIPTION Mains voltage Battery charge percentage Mains frequency Total battery voltage UPS output voltage Applied load perce...

Страница 12: ...switched on the load is disconnected in the event of a mains blackout If the input mains deviates from the established tolerances the UPS automatically switches to Stdby mode and disconnects the load...

Страница 13: ...full display of the status of the UPS via USB or RS232 For a list of possible configurations available to the user refer to the UPS Configuration paragraph INSTALLATION OPERATIONS 1 Connect one of the...

Страница 14: ...attery discharge 1 65000 sec in 1 sec steps Battery low warning Estimated autonomy time remaining for the battery low warning 3 min 1 255 min in 1 min steps Battery test Interval of time for the autom...

Страница 15: ...UPS refer to the manual provided 2 TXD 3 RXD 4 Programmable input default disabled 5 GND 6 Power supply DC Imax 20mA 7 Programmable input default disabled 8 Programmable output default low battery pr...

Страница 16: ...INS FAILURE THE BATTERY PACK IS VERY HEAVY USE EXTREME CAUTION WHEN REPLACING IT 1 Set the UPS in battery swap mode by pressing and holding both the ON and SEL button for 4 seconds See par USE Operati...

Страница 17: ...in the same number and type of batteries see the label located on the battery pack near the connector 5 Insert the new battery pack into the compartment sliding it into the UPS Replace the battery pac...

Страница 18: ...IS NOT POWERED THE UPS IS IN STAND BY MODE Press the ON button on the front panel to power the loads NO CONNECTION TO THE LOAD Check the connection to the load THE UPS IS OPERATING FROM THE BATTERY DE...

Страница 19: ...HOWS ONE OF THE FOLLOWING CODES F04 L04 THE TEMPERATURE OF THE HEATSINKS INSIDE THE UPS IS TOO HIGH Check that the temperature of the environment in which the UPS is located does not exceed 40 C THE B...

Страница 20: ...mance or prevent certain functions from being used CODE DESCRIPTION A06 Sensor1 temperature under 0 C A08 Sensor2 temperature under 0 C A54 Load percentage greater than the user threshold set A61 Repl...

Страница 21: ...he load being powered by the bypass line this procedure is excluded for locks due to serious persistent overloads and short circuits CODE DESCRIPTION L04 Heatsink over temperature L05 Temperature sens...

Страница 22: ...ing 110 load 150 From mains locked after 10 sec From battery locked after 5 sec Load overload 150 From mains locked after 1 sec From battery locked 0 5 sec OTHER DATA Leakage current towards ground mA...

Страница 23: ...0MNVST800RUENUA...

Отзывы: