INSTALLATION
I
NITIAL CONTENT CHECK
After opening the packaging, it is first necessary to check the contents.
The package must contain:
UPS
Schuko power cable - IEC 10A
2 IEC 10A connection cables
USB cable
RS232 cable
User manual CD + Safety manual
I
NSTALLATION ENVIRONMENT
The UPS and the Battery Box must be installed in ventilated, clean environments which are sheltered from bad weather.
The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table.
The ambient temperature, whilst the UPS is in operation, must remain between 0 and 40°C, and the UPS must not be
positioned in places which are exposed to direct sunlight or to hot air.
The recommended operating temperature for the UPS and the batteries is between 20 and 25°C. The actual
operating life of the batteries is 5 years on average with an operating temperature of 20°C. If the operating
temperature reaches 30°C, the operating life is halved.