16
When removing the rear outlet cap; retain the 4-screws as
these are required to attach the rear-flue terminal to the
appliance (fig. 18).
Fig.17
Fig.18
Seal the flue assembly to the wall using cement or a suitable
alternative that will provide satisfactory weatherproofing. The
exterior wall trim can now be fitted.
Part No.
Description
Length
20132064
Rear flue terminal
825mm
4.5.2 CONCENTRIC VERTICAL FLUE
Using fig.20 as a reference, cut a 110mm diameter hole in
the roof and/or ceiling to facilitate the route of the vertical flue
system.
NOTE:
ensure that the top of the appliance - if already
in position - is covered and protected from the possibility of any
dust or debris falling or entering the appliance via the flue outlet.
Fit the appropriate flashing to the roof and insert the vertical flue
terminal through the flashing from outside, ensuring that the
collar of the terminal is located over the outlet of the flashing.
The fixing holes for the appliance wall mounting bracket should
now be drilled and plugged. An appropriate type and quantity
of fixing should be used to ensure that the bracket is mounted
securely. Once the bracket has been secured to the wall, mount
the appliance onto the bracket.
If the vertical flue system requires additional extensions or bends,
connect these to the vertical terminal, ensuring the following:
- the maximum permitted flue length is not exceeded
- reductions to the maximum flue length have been made for
any bends that are used on the vertical flue system
- any horizontal sections of the flue system, incorporate a
3-degree fallback to the appliance
- the entire flue system is fully supported and secured using
the appropriate brackets
- if/when an extension is cut to a shorter length, ensure that
the excess length is cut from the plain end of the extension,
and that any burrs or rough edges are removed
- all seals are properly located before assembling or connecting
the flue system.
IMPORTANT:
The VX flue terminal is supplied with a sachet of
silicone lubricant; smear a small amount of the lubricant around
both inner and outer connections, at both ends of the vertical
flue connector (supplied with the VX terminal).
NOTE:
The appliance incorporates a ‘click-fit’ flue connection
(see fig. 19). Ensure that both screws ‘
C
’ (fig. 12) on the ‘click-fit’
have been slackened off. Ensure that the connector is correctly
aligned with the ‘click-fit’ and insert it into the ‘click-fit’ until it
clicks into position (this is when the tabs at points ‘
A
’ are located
in the groove of the vertical flue connector - see fig. 19). Both
screws (
C
) should now be tightened.
NOTE:
If more convenient, the vertical flue connector can be
attached to the vertical flue terminal/extension before connecting
it to the appliance.
NOTE
Additional bends and/or extensions can be connected to the
terminal connector if desired, however if additional bends are
fitted, a reduction must be made to the maximum flue length
(see table below).
vertical
connection
A
A
C
C
B
flange installed
as standard
Fig.19
Reduction for bends
Bend
Reduction in maximum flue length for each bend
45º bend
1.0 metre
90º bend
1.0 metre
Vertical flue terminal and accessories
Code
Description
Length
20122763
XV vertical Flue kit
1000mm
20132050
Pitched Roof Flashing
N/A
20135582
Flat Roof Flashing
N/A
20132059
90-Degree Bend
N/A
20132058
45-Degree Bend x 2
N/A
20132060
0.5-Metre Extension
500mm
20132061
1.0-Metre Extension
1000mm
20132062
2.0-Metre Extension
2000mm
20131979
Telescopic Extension
372/519mm
20135585
Wall Brackets
N/A
Fig. 20