background image

24

7.1  CHECKING APPLIANCE OPERATION

When carrying out any repairs or servicing to the appliance, 

the relevant commissioning procedure must be undertaken to 

ensure the continued safe operation of the appliance. Particular 

attention should be made to ensure gas tightness, water tight-

ness and the electrical integrity of the appliance.

7.2  APPLIANCE MODES OF OPERATION

NOTE

There must be sufficient system water pressure (min. 0.5 bar) 

to ensure the water pressure switch is activated. If there is in-

sufficient system pressure the pump and fan will be prevented 

from operating and the low-pressure fault code will be indicated.

7.2.1 SELECTOR SWITCH IN THE OFF/RESET POSITION

When the selector switch is in the OFF/RESET position, the 

following functions are active.

Active functions

:

• 

frost-protection system

• 

pump & actuator anti-block.

7.2.2 ON-BOARD FUNCTIONS

•  CO FUNCTION:

 the CO function when activated, will allow the 

appliance to run at CH maximum, DHW maximum or minimum 

output whilst a combustion analysis check or a mechanical gas 

valve calibration is being carried out. Whilst the CO function 

is active, all other functions are disabled (minimum power 

operating period, anti-cycle, set-point, etc). Once enabled, 

the CO function will remain active for a 15-minute period, or 

until the function is manually deactivated. 

• FROST-PROTECTION: 

this function is only active when 

there are no requests for heating or HW. If the temperature 

drops below 5°C, the boiler will operate on minimum power 

until the temperature of the thermistors reaches 35°C for CH 

and 55°C for DHW. Thereafter the pump & fan will over-run 

for 30-seconds.

•  ANTI-CYCLE FUNCTION:

 the anti-cycle function ensures the 

burner remains switched off for at least 3-minutes after the 

set-point hysterisis (set-point + 5-deg) for CH heat request. 

•  PUMP ANTI-BLOCK FUNCTION: 

when there has been no 

heating or HW request for 24-hours, the anti-block cycle is 

activated. The pump will be activated for a period of 30-seconds.

•  ACTUATOR ANTI-BLOCK FUNCTION: 

when there has been 

no heating or HW request for 24-hours, the anti-block cycle 

is activated. The divertor valve actuator will motor briefly to 

the heating position, and then back to the DHW position. The 

pump will run briefly.

•  SARA function:

 the SARA function permits the boiler (when 

the set-point is within the SARA range) to automatically adjust 

(raise) the heating flow outlet temperature should the room 

thermostat contacts remain closed for more that 20-minutes.

•  DHW PRE-HEAT FUNCTION:

 when the DHW pre-heat func-

tion is enabled, the appliance will light periodically to maintain 

the temperature of the DHW heat exchanger. When the 

DHW thermistor and the primary thermistor fall below 35°C 

and 55°C respectively, the boiler will fire on m25% 

power until the primary thermistor exceeds 55°C. Thereafter 

the pump will over-run for a period of 30-seconds.

7.2.3 HEATING MODE

With the selector switch in the heating & hot water position 

and any additional controls (time clock, programmer, room 

thermostat, etc.) calling for heat, the appliance will operate 

in the heating mode. The pump and fan will be activated via 

the flow temperature sensor. When the fan is sensed to be 

operating correctly (tacho signal), the ignition sequence com-

mences. Ignition is sensed by the electronic circuit to ensure 

flame stability at the burner. Once successful ignition has been 

achieved, the electronic circuitry increases the gas rate to 75% 

for a period of 15 minutes.

The speed of the fan and therefore the output of the boiler is 

determined by the temperature of the water sensed by the 

flow temperature sensor, consequently a high temperature at 

the flow sensor results in a lower fan speed. As the water tem-

perature increases, the temperature sensors – located on the 

flow pipe of the boiler – reduce the fan speed via the electronic 

circuitry. Depending on the load, either the water temperature 

will continue to rise until the set point is achieved or the water 

temperature will fall whereby fan speed will increase relative to 

the output required. When the boiler has reached the set point 

(+ hysterisis), the burner will switch off. 

SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING

The built-in anti-cycle device prevents the burner from re-

lighting for approximately 3-minutes. When the temperature 

of the flow sensor falls below the set point (- hysterisis), the 

burner will re-light.

NOTE

If the spark/sensing electrode does not sense ignition the appli-

ance will re-attempt ignition a further 4-times then go to lockout. 

When the set-point has been reached (the position of the heating 

temperature selector) as measured at the primary thermistor, the 

appliance will begin the modulation phase whereby the fan and 

gas valve will continuously modulate to maintain the set-point.

If the temperature continues to rise and exceeds the set-point 

by 5°C (hysterisis), the burner will shut down. A new ignition 

sequence will be enabled when the 3- minute anti-cycle has 

been performed and the temperature at the primary thermistor 

has dropped 5°C (hysterisis) below the set-point.

7.2.4 DHW MODE

With the selector switch in either the hot water only or heating 

& hot water position, the appliance will operate in the hot water 

mode whenever a DHW outlet is opened. A flow rate exceeding 

2-litres per minute will activate the DHW flow switch whereupon 

the pump and fan will be activated via the flow temperature 

sensor. When the fan is sensed to be operating correctly (tacho 

signal), the ignition sequence commences. Ignition is sensed 

by the electronic circuitry to ensure flame stability at the burner. 

Once successful ignition has been achieved, the electronic 

circuit allows the gas rate to achieve the modulation value.

NOTE

When the request for heating and/or hot water has been satis-

fied, the appliance pump and fan may continue to circulate to 

dissipate any residual heat within the appliance.

ATTENTION

Gas type and appliance output 

must be set 

according to the 

specific appliance specification. Vokèra accepts no responsi-

bility if the gas type is not correctly adjusted according to the 

respective appliance specification as detailed on the appliance 

data badge.

7.3  CHECKING THE CO

2

 AND ADJUSTING THE 

GAS VALVE

Isolate the appliance from the electrical supply and remove the 

appliance casing as described in 4.7.1, to gain access to the 

printed circuit board, locate and open the closing plug on the 

dash board (

L2

), Restore the electrical supply to the boiler and 

switch the boiler to the OFF mode. locate and press the CO but-

ton (see fig. 44 pos. 

SW1

). Press the button the number of times 

according the function requirement as par 7.3.1.

Set the flue gas analyser to read CO

2

 and insert the probe into 

the flue analysis test point (

Y1-Z1

 fig. 41).

L2

Fig. 44

1

12

CN11

1

4

CN10

1

7

CN9

CN6

CN5

CN12

1

CN4

1

3

CN3

1

2

CN2

1

6

CN1

1

FA1

FA2

orange

F.S. (1)

JP1

JP2

JP3

JP4

JP5

JP6

JP7

JP8

CN15

P3

P2

P1

CN13

CN14

SW1

P4

F1

3.15A T

CN7

AKL05 GAR

CN8

SW1

use the supplied 

screwdriver to push the 

CO botton (SW1)

Содержание Vokera Compact 25A

Страница 1: ...USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Compact A High efficiency combi b...

Страница 2: ...E CO2 AND ADJUSTING THE GAS VALVE 31 Commissioning checklist 32 Benchmark 33 35 1 THINGS YOU SHOULD KNOW 1 1 1 GAS APPLIANCES 1 1 2 ELECTRICAL SUPPLY 1 1 3 GUARANTEE REGISTRATION CARD 1 1 4 APPLIANCE...

Страница 3: ...been designed to meet and exceed the very latest standards in gas central heating technol ogy and if cared for will give years of reliable use and efficiency Please therefore take some time to read t...

Страница 4: ...for standard central heating The automatic temperature control function SARA is set within the blank bullet points The display shows the temperature values Pressure gauge shows the current pressure o...

Страница 5: ...the boiler are turned on Turn the mode selector switch to the ON position When there is a request for heating or hot water via the time clock or pro grammer the boiler will begin an ignition sequence...

Страница 6: ...l not exceed the maximum Filling the siphon before using the appliance and the use of a safety cut off device inside the siphon prevent exhaust gases from being released into the environment Repeat du...

Страница 7: ...your boiler has been installed with the Vok ra mechanical clock it can be used and adjusted as follows Setting the time The time of day can be set by grasping the outer edge of the black dial and tur...

Страница 8: ...EU Low voltage directive 2014 35 EU Directive 2009 125 EC Ecodesign for energy using appliances Regulation EU 2017 1369 Energy labeling Delegated Regulation EU No 811 2013 Delegated Regulation EU No 8...

Страница 9: ...boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appl...

Страница 10: ...itres Maximum system volume 74 litres Pre charge pressure 1 bar 2 6 Dimensions Height mm 715 Width mm 405 Depth mm 250 Dry weight kg 29 29 29 2 7 Clearances Sides 12mm Top 150mm from casing or 25mm ab...

Страница 11: ...art load elmin 10 4 12 8 13 1 W In Stand by mode PSB 2 4 2 0 2 4 W Other parameters Stand by heat loss Pstby 40 0 35 0 35 0 W Pilot flame energy consumption Pign W Annual energy consumption QHE 53 63...

Страница 12: ...lcony level 300 mm J From a surface or boundary facing the terminal 600 mm K From a terminal facing a terminal 1200 mm L From an opening in the car port into the building 1200 mm M Vertically from a t...

Страница 13: ...POINT A method for initial filling of the system and replacing water lost during servicing etc directly from the mains supply is provided see fig 9 This method of filling complies with the current Wa...

Страница 14: ...efittedinaccordancewiththeInstituteofGasEngineers publication IGE UP 7 Guide for Gas Installations in Timber Frame Buildings 3 10 WATER TREATMENT Vokera recommend that water treatment be carried out i...

Страница 15: ...uthority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the...

Страница 16: ...em ordownloadtheinstructionsfromtheVokera website The appliance flue outlet elbow can be rotated through 360 on its vertical axis In addition the flue may be extended from the outlet elbow in the hori...

Страница 17: ...ting an extension to the required length you must ensure that the excess is cut from the plain end of the extension see fig 12 15 Remove any burrs and check that all seals are located properly You mus...

Страница 18: ...the appropriate brackets if when an extension is cut to a shorter length ensure that the excess length is cut from the plain end of the extension and that any burrs or rough edges are removed allseal...

Страница 19: ...nal waste water pipework in accordance with BS6798 BS6798 provides comprehensive instruction and advice on all permissible condensate disposal methods notwithstanding this it is essential that the fol...

Страница 20: ...l forwards and down Locate the terminal block cover fig 26 NOTE The appliance is supplied with a plug play controls lead that enables quick and easy connection to various Vok ra controls refer to Sect...

Страница 21: ...static heads Adjust radiator return valves and any branch circuit return valves until the individual return temperatures are correct and are approximately equal 5 11 1 REGULATING THE DHW FLOW RATE The...

Страница 22: ...g electrodes insulation panelling etc avoid direct contact with any cleaning appliance e g brushes aspira tors blowers etc This component does not need any maintenance please do not remove it from its...

Страница 23: ...cal plug and leads from the gas valve slacken and unscrew gas valve inlet and outlet connections Please note the sealing washers Q must be discarded and replaced with new sealing washers Unscrew gas p...

Страница 24: ...nd or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order ensuring the cartridge is facing the correct way...

Страница 25: ...ch B2 Using a small screwdriver gently ease the flow restrictor C2 from its seating Replace in the reverse order Ensure all seals are in good condition taking care to ensure they are replaced correctl...

Страница 26: ...increases the gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow temperature sensor...

Страница 27: ...isplay shows ACO and the boiler operates at maximum heating Insert the flue gas analyser probe into the flue gas test point see fig 41 Operate the boiler in combustion analysis mode see 7 3 1 and comp...

Страница 28: ...min output Min 25 CO function max temp C 90 CO re light temp C 78 CO function time 15 min Flow NTC max temp C 90 High limit thermostat C 105 Flue NTC max temp C 125 Maximum differential C 35 IGNITION...

Страница 29: ...ctor switch to the ON position press the CO button once the display will then scroll through the fan speeds along with the relevant icon 7 10 2 THERMOREGULATION To set the temperature regulation curve...

Страница 30: ...nge JP7 removed T45 Maximum set point for low T range JP7 inserted Fig 48 1 12 CN11 1 4 CN10 1 7 CN9 CN6 CN5 CN12 1 CN4 1 3 CN3 1 2 CN2 1 6 CN1 1 FA1 FA2 orange F S 1 JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8 C...

Страница 31: ...xternal time control The kit is comprised of the following lower cover mechanical clock wiring harness instructions Isolate the appliance from the electrical supply remove the boiler casing see 4 7 1...

Страница 32: ...AMP black red blue brown 4 4 Connector clock AKL05 GAR CN8 FUNCTIONAL DIAGRAM Fig 51 NOTE L N E connection is advisable AKL05GAR Main PCB with vis medium integrated P1 Selector switch and heating pot...

Страница 33: ...THE CO2 AND ADJUSTING THE GAS VALVE refer to the Section 7 3 Fig 52 BS 5440 PARTS 1 2 FLUES VENTILATION REQUIREMENTS BS 5449 PART 1 FORCED CIRCULATION OF HOT WATER SYSTEMS BS 5482 PART 1 DOMESTIC BUTA...

Страница 34: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Страница 35: ...ommissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarantee...

Страница 36: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Страница 37: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Страница 38: ...structions must be provided e g Benchmark Service Record If this condition is not met the period of warranty will extend to only 12 months from date of installation By registering your appliance you w...

Страница 39: ...from a Trading Standards Authority or a Citizen Advice Bureaux Your Personal Details Vok ra takes care of your personal details in order to protect your privacy Below we detail how we use any data you...

Страница 40: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0344 391 0999 F 0344 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited...

Отзывы: