Start-up, calibration and operation of the burner
6.9
Stopping of the burner
The burner can be stopped by:
intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
working on the switch “
0-AUTO
” of Fig. 30 at page 31;
removing the transparent protection that covers the Operator
Panel.
6.10
Final checks (with burner operating)
Tab. P
Open the thermostat/pressure switch TL
Open the thermostat/pressure switch TS
The burner must stop
Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
Turn the air pressure switch to the maximum end of scale
position.
The burner must stop in lockout
Disconnect the minimum gas pressure switch connector.
The burner must not start
Disconnect the ionisation probe wire
The burner must stop in lockout due to firing failure
WARNING
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
Содержание RS 160/E O2 BLU
Страница 2: ...Translation of the original instructions...
Страница 44: ...20164541 42 GB Appendix Electrical panel layout 0 1 0 0 1 1 1 1 0 2 0 0 3 3 3 4 3 5 3 3 3 3 3 3 3 3 3 3 4 3...
Страница 45: ...43 20164541 GB Appendix Electrical panel layout...
Страница 46: ...20164541 44 GB Appendix Electrical panel layout 0 0 0 1 2 3 2 3 2 4 2 5 2 2 2 2 2 32 3 2 62 6 6 3 2 2 4 2...
Страница 47: ...45 20164541 GB Appendix Electrical panel layout...
Страница 48: ...20164541 46 GB Appendix Electrical panel layout...
Страница 49: ...47 20164541 GB Appendix Electrical panel layout...
Страница 50: ...20164541 48 GB Appendix Electrical panel layout 0 0 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 51: ...49 20164541 GB Appendix Electrical panel layout 0 1 0 1 0 2 0 3 0 0 0 0 0 10 1 0 40 4 4 1 0 0 2 0 5...
Страница 55: ...53 20164541 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...
Страница 57: ......
Страница 58: ......
Страница 59: ......