background image

31 

20164541

GB

Start-up, calibration and operation of the burner

6.3

Burner start-up  

Feed electricity to the burner via the disconnecting switch on the

boiler panel.
Close the thermostats/pressure switches and turn the switch to

Fig. 30 “

AUTO”

.

6.4

Burner adjustment

6.4.1

Firing output

According to the regulation EN 676.

Burners with MAX output up to 120 kW

Ignition can be performed at the maximum operation output level.
Example:

max. operation output:

120 kW

max. firing output:

120 kW

Burners with MAX output above 120 kW

Ignition must be performed at a lower output than the max. oper-
ation output.
If ignition output does not exceed 120 kW, no calculations are re-
quired. If ignition output exceeds 120 kW, the regulations pre-
scribe that the value be defined according to the control box
safety time "ts":
for ts = 3 s, ignition output must be equal to, or lower than, 1/3 of
max. operation output.
Example:
MAX operation output of 450 kW.
The ignition output must be equal to, or less than, 150 kW with
ts = 3 s
In order to measure the ignition output:

disconnect the plug-socket 7)(Fig. 5 at page 12) on the ioni-
sation probe cable (the burner will fire and then go into lock-
out after the safety time has elapsed);

perform 10 ignitions with consecutive lockouts;

on the meter, read the quantity of gas burned:
this quantity must be equal to, or lower than, the quantity
given by the formula, for ts = 3 s:

Vg

volume supplied in ignitions carried out (Sm

3

)

Qa

ignition delivery (Sm

3

/h)

n

number of ignitions (10)

ts

safety time (sec)

Example for gas G 20 (9.45 kWh/Sm

3

):

ignition output 150 kW corresponding to 15.87 Sm

3

/h.

After 10 ignitions with lockout, the delivery indicated on the meter
must be equal to, or less than:

6.4.2

Maximum output

The MAX output must be set within the firing rate (Fig. 2 at
page 9).

Gas adjustment

Measure the gas delivery on the meter. 
As a general rule, this value can be found on Tab. O at page 27,
just read the gas pressure on the pressure gauge (Fig. 37 at
page 37
) and follow the indications given on page 27.

If it is necessary to reduce it, lower the output gas pressure
via the pressure adjuster located beneath the gas valve.

If it needs to be increased, increase the output gas pres-
sure via the adjuster.

Air adjustment

If necessary vary the degrees of the air servomotor.

6.4.3

Minimum output

The MIN output must be set within the firing rate (Fig. 2 at
page 9).

DANGER

Make sure that the lights or testers connected to
the solenoids, or the pilot lights on the solenoids
themselves, indicate that no voltage is present. 
If voltage is present, then 

immediately

 stop the

burner and check the electrical wiring. When the
burner starts, check the direction of the rotation of
the motor, as shown in Fig. 30.
As soon as the burner starts up, go in front of the
cooling fan of the fan motor and check it is rotating
anticlockwise.
If this is not the case:

place the switch of Fig. 30 in position 

“0”

 and

wait for the control box to carry out the
switch-off phase;

disconnect the burner from the electrical sup-
ply;

invert the phases on the three-phase power
supply.

0

AUTO

 Fig. 30

20110442

Vg =

3600

Qa 

(max. burner delivery)

 x n x ts

Vg =

3600

15.87 x 10 x 3

= 0.132 Sm

3

 

Содержание RS 160/E O2 BLU

Страница 1: ...lation use and maintenance instructions 20164541 5 03 2021 Forced draught gas burners Modulating operation CODE MODEL TYPE 20166113 20164535 RS 160 E O2 BLU 843T1 20171269 20166368 RS 200 E O2 BLU 110...

Страница 2: ...Translation of the original instructions...

Страница 3: ...erminal ratings cable lengths and cross sectional areas 16 4 14 Oxygen sensor QGO20 optional 17 4 14 1 Technical data QGO20 18 4 15 Calibration of the thermal relay 19 5 Installation 20 5 1 Notes on s...

Страница 4: ...urner operating 34 6 11 Description of O2 trim control optional 35 6 11 1 Operating principle of O2 trim control 35 7 Maintenance 36 7 1 Notes on safety for the maintenance 36 7 2 Maintenance programm...

Страница 5: ...d according to the European Directives GAR 2016 426 EU Gas Devices Regulation MD 2006 42 CE Machine Directive LVD 2014 35 EU Low Voltage Directive EMC 2014 30 EU Electromagnetic Compatibility Such pro...

Страница 6: ...ied out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wi...

Страница 7: ...f damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreasonable...

Страница 8: ...ce Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the specific pur...

Страница 9: ...50Hz 3 230V 50Hz 230V 50 60Hz 110V 50 60Hz Heavy oil E Electronic cam EV Electronic cam and variable speed with Inverter M Mechanical cam P Proportional air gas valve S L LS N Head TC Standard head T...

Страница 10: ...II2ELL3B P FR I2Er II2Er3P AT BG CH CZ DK EE ES FI GB GR HU IE IS IT LT LV NO PT RO SE SI SK TR I2H II2H3B P II2H3P Model RS 160 E O2 BLU RS 200 E O2 BLU Output 1 Max kW Mcal h 930 1860 800 1600 1380...

Страница 11: ...Fig 2 The minimum output must not be lower than the minimum limit of the diagram Fig 1 D1206 mm A B C D E F 1 G H I L M N O RS 160 E O2 BLU 681 366 315 650 1035 373 503 222 435 1442 1587 230 141 260...

Страница 12: ...it is necessary to reduce the output of the burner The reduction in output is accompanied by a reduction in the combustion chamber pressure Qr reduced output H1r reduced pressure Example 5 reduction...

Страница 13: ...boiler is EC type approved for boilers or ovens with combustion chambers of very different di mensions compared to those shown in the diagram of Fig 4 pre liminary checks are recommended 4 9 Burner e...

Страница 14: ...ressure switch differential operating type 20 Slide bars for opening the burner and inspecting the com bustion head 21 Gas pressure test point and head fixing screw 22 Air pressure socket 23 Terminals...

Страница 15: ...must also be followed avoid conditions that can favour the development of conden sate and humidity Otherwise before switching on again make sure that the entire control box is perfectly dry Static cha...

Страница 16: ...nal 6 3 AT Main fuse of perm network external Max 16 AT Undervoltage Safety switch off from operating position to mains voltage Restart when mains voltage picks up AC 186 V AC 188 V Oil pump magnetic...

Страница 17: ...supply of the actuator is switched off The housing cover may only be removed for short periods of time for wiring or when making the addressing In similar cas es make sure that dust or dirt does not...

Страница 18: ...e lengths 10 m fino a QGO20 Cross sectional areas Refer to description of QGO20 Analog inputs Air temperature detector Pt1000 LG Ni1000 Flue gas temperature Pt1000 LG Ni1000 QGO20 Refer to data sheet...

Страница 19: ...ning the inlet and outlet allow the sensor to cool down for at least 1 hour Mount the sensor such that the connecting part head to flange is free so that the exchange of air is ensured Otherwise measu...

Страница 20: ...e gas velocity only with AGO20 1 10 m s Fuel type Fuel oil EL or Natural gas H Measuring range 0 2 20 9 O2 Permissible cable length Max 100 m Wire diameter 10 m Power supply lines Net cable Cable diam...

Страница 21: ...calibration 2 see the table in the wiring diagram To reset in case of an intervention of the thermal relay press the RESET button 1 of Fig 10 The red TEST button 3 opens the NC 95 96 contact and stop...

Страница 22: ...e free from hazardous mixes e g chloride fluoride halo gen if present it is highly recommended to carry out cleaning and maintenance more frequently WARNING The handling operations for the burner can...

Страница 23: ...e others With the kit this second group of tubes is substituted so that all the tubes are the same After assembling the kit check its efficiency by measuring the flue gases and CO 5 5 2 Boring the boi...

Страница 24: ...ater cooled frontal a refractory cover is not necessary 11 12 Fig 17 unless expressly requested by the boiler manufacturer 5 6 Positioning probe electrode If in the previous check the position of the...

Страница 25: ...nect the probe and electrode leads then unthread the burner completely from the guides Once this operation has been carried out fix the flange 9 to the boiler plate interposing the insulating gasket 8...

Страница 26: ...air R2 In the diagram Fig 20 find the notch at which to adjust both air and central air External air R2 adjustment Rotate the screw 4 Fig 18 Fig 19 until the notch you have found corresponds with the...

Страница 27: ...he position shown in Fig 17 insert the probe and electrode cables then slide the burner as far as the pipe coupling burner in the position shown in Fig 21 connect the socket of the maximum gas pressur...

Страница 28: ...trol is compulsory for burners with maximum outputs over 1200 kW 9 Gasket for flanged versions only 10 Pressure adjuster 11 Train burner adaptor supplied separately P2 Upstream pressure of valves adju...

Страница 29: ...esult you want Read the corresponding output on the left Example with natural gas G 20 Maximum output operation Gas pressure at test point 1 Fig 27 16 0 mbar Pressure in combustion chamber 3 0 mbar 16...

Страница 30: ...operation 1600 kW Gas pressure at output of 1600 kW 13 0 mbar Pressure in combustion chamber 3 0 mbar 13 3 0 16 0 mbar pressure required at test point 1 Fig 27 WARNING The heat output and gas pressure...

Страница 31: ...for intermittent use This means they should compulsorily be stopped at least once every 24 hours to enable the control box to per form checks of its own start up efficiency Normally burner stopping is...

Страница 32: ...rac teristics label Bleed the air from the piping of the gas train connecting a plastic tube to the pressure test point 1 Fig 26 of the mini mum gas pressure switch Take the vent tube outside the buil...

Страница 33: ...ignitions 10 ts safety time sec Example for gas G 20 9 45 kWh Sm3 ignition output 150 kW corresponding to 15 87 Sm3 h After 10 ignitions with lockout the delivery indicated on the meter must be equal...

Страница 34: ...the pressure gauge is shown in Fig 31 The standard configuration is that with the air pressure switch connected in absolute mode Note the presence of a T connec tion not supplied In certain applicatio...

Страница 35: ...educes the output as far as the MIN value The burner switches off when the request for heat is lower than the heat supplied by the burner at MIN output The thermostat pressure switch TL opens and the...

Страница 36: ...rating Tab P Open the thermostat pressure switch TL Open the thermostat pressure switch TS The burner must stop Turn the gas maximum pressure switch knob to the mini mum end of scale position Turn the...

Страница 37: ...positions of these actuators are cal culated from some other load point on the ratio control curves Hence due to the parameterized ratio control curves the air reg ulating actuators are in a fixed rel...

Страница 38: ...dicators that are activated when the electrical supply arrives 7 2 3 Checking and cleaning Combustion The optimum calibration of the burner requires an analysis of the flue gases Significant differenc...

Страница 39: ...g the air and gas pressure on the combustion head To carry out this operation a pressure gauge must be used to measure the air and gas pressure at the combustion head as shown in Fig 37 7 2 6 Safety c...

Страница 40: ...he burner up to approximately 100 mm from the pipe coupling reconnect the cables and slide in the burner until it comes to a stop connect the socket of the maximum gas pressure switch replace the scre...

Страница 41: ...th the burner Software interface kit A Appendix Accessories Burner Thickness mm Code RS 160 200 E O2 BLU 135 3000722 Burner Code RS 160 200 E O2 BLU 3010094 Burner Type dB A Code RS 160 200 E O2 BLU C...

Страница 42: ...transformer Gas trains in compliance with EN 676 Please refer to manual Burner Code RS 160 200 E O2 BLU 20045187 Burner Code RS 160 200 E O2 BLU 3010377 Burner Code RS 160 200 E O2 BLU 20044117 ATTEN...

Страница 43: ...perational layout LMV52 6 Operational layout LMV52 7 Operational layout LMV52 8 Operational layout LMV52 9 Operational layout LMV52 10 Operational layout LMV52 11 Electrical connection set by installe...

Страница 44: ...20164541 42 GB Appendix Electrical panel layout 0 1 0 0 1 1 1 1 0 2 0 0 3 3 3 4 3 5 3 3 3 3 3 3 3 3 3 3 4 3...

Страница 45: ...43 20164541 GB Appendix Electrical panel layout...

Страница 46: ...20164541 44 GB Appendix Electrical panel layout 0 0 0 1 2 3 2 3 2 4 2 5 2 2 2 2 2 32 3 2 62 6 6 3 2 2 4 2...

Страница 47: ...45 20164541 GB Appendix Electrical panel layout...

Страница 48: ...20164541 46 GB Appendix Electrical panel layout...

Страница 49: ...47 20164541 GB Appendix Electrical panel layout...

Страница 50: ...20164541 48 GB Appendix Electrical panel layout 0 0 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...

Страница 51: ...49 20164541 GB Appendix Electrical panel layout 0 1 0 1 0 2 0 3 0 0 0 0 0 10 1 0 40 4 4 1 0 0 2 0 5...

Страница 52: ...20164541 50 GB Appendix Electrical panel layout 0 12 34 5 5 5 5 5 6 6 6 7 6 6 6 6 6 6 6 6 6 6 6 7 6 0 0 34 34 3 0 12 3 0 12 3 0 12...

Страница 53: ...51 20164541 GB Appendix Electrical panel layout 01 2 34 5 5 5 5 5 6 6 6 7 6 6 6 6 6 6 6 6 6 6 6 7 6 01 01 0 2 34 0 2 34 0 2 34 2 2...

Страница 54: ...GB Appendix Electrical panel layout 0 1 2 10 3 3 6 7 6 7 6 7 8 6 7 6 7 09 0 4 09 6 7 6 87 6 7 6 87 09 5 5 8 6 7 6 7 8 6 7 6 7 09 0 5 5 8 6 7 0 0 0 0 3 0 0 0 0 0 0 0 2 2 0 0 0 0 0 3 0 0 0 0 1 2 0 0 2...

Страница 55: ...53 20164541 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...

Страница 56: ...ol G30 Probe for air temperature control H1 Green indicator POWER ON H2 Green indicator FUEL ON KM Motor contactor ION Ionisation probe MV Fan motor K3 K3 relay free contact BURNER LOCK OUT K6 K6 rela...

Страница 57: ......

Страница 58: ......

Страница 59: ......

Страница 60: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: