Technical description of the burner
Electrical connection of ionization probe and flame sensor
It is important for signal transmission to be almost totally free
of any disturbances or loss:
• always separate the detector cables from the other cables:
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
• Respect the allowed cable lengths.
• The ionisation probe is not protected against the risk of elec-
trocution. When connected to the electricity supply, the ionisa-
tion probe must be protected against any accidental contact.
• Position the ignition electrode and the ionisation probe so
that the ignition spark cannot form an arc on the probe
(risk of electric overcharge).
Technical data
Tab. G
LMV52...
base control box
Mains voltage
AC 230V -15% / +10%
Mains frequency
50 / 60 Hz ±6 %
Power absorption
< 30W (normal)
Safety class
I, with components in compliance with II and III, according to
DIN EN 60730-1
Load on ‘input’
terminals
F1 unit fuse (internal)
6.3 AT
Main fuse of perm. network (external)
Max. 16 AT
Undervoltage
• Safety switch-off from operating position to
mains voltage
• Restart when mains voltage picks up
< AC 186 V
> AC 188 V
Oil pump / magnetic clutch (nominal voltage)
• Nominal current
• Power factor
2A
cos
> 0.4
Air pressure switch test valve (nominal voltage)
• Nominal current
• Power factor
0.5A
cos
> 0.4
Load on ‘output’
terminals
Total load on the contacts:
• Mains voltage
• Total unit input current (safety circuit)
load on contacts due to:
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
AC 230 V -15 % / +10 %
Max. 5 A
Single contact loading:
Fan motor contactor (nominal voltage)
• Nominal current
• Power factor
1A
cos
> 0.4
Alarm output (nominal voltage)
• Nominal current
• Power factor
1A
cos
> 0.4
Ignition transformer (nominal voltage)
• Nominal current
• Power factor
2A
cos
> 0.2
Fuel gas valve (nominal voltage)
• Nominal current
• Power factor
2A
cos
> 0.4
Fuel oil valve (nominal voltage)
• Nominal current
• Power factor
1A
cos
> 0.4
Cable lengths
Main line
Max. 100 m (100 pF/m)
Environmental
conditions
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
DIN EN 60721-3-3
Classe 3K3
Classe 3M3
-20...+60°C
< 95% RH
Содержание RS 160/E O2 BLU
Страница 2: ...Translation of the original instructions...
Страница 44: ...20164541 42 GB Appendix Electrical panel layout 0 1 0 0 1 1 1 1 0 2 0 0 3 3 3 4 3 5 3 3 3 3 3 3 3 3 3 3 4 3...
Страница 45: ...43 20164541 GB Appendix Electrical panel layout...
Страница 46: ...20164541 44 GB Appendix Electrical panel layout 0 0 0 1 2 3 2 3 2 4 2 5 2 2 2 2 2 32 3 2 62 6 6 3 2 2 4 2...
Страница 47: ...45 20164541 GB Appendix Electrical panel layout...
Страница 48: ...20164541 46 GB Appendix Electrical panel layout...
Страница 49: ...47 20164541 GB Appendix Electrical panel layout...
Страница 50: ...20164541 48 GB Appendix Electrical panel layout 0 0 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 51: ...49 20164541 GB Appendix Electrical panel layout 0 1 0 1 0 2 0 3 0 0 0 0 0 10 1 0 40 4 4 1 0 0 2 0 5...
Страница 55: ...53 20164541 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...
Страница 57: ......
Страница 58: ......
Страница 59: ......