27
20164541
GB
Installation
5.9.2
Gas train
Type-approved in accordance with EN 676 and supplied sepa-
rately from the burner.
To select the correct model of the gas train, refer to the “burner-
gas train combination” manual supplied.
5.9.3
Gas train installation
The gas train can enter the burner from the right or left side, de-
pending on which is the most convenient, see Fig. 26.
The gas train must be connected to the gas attachment
1)(Fig. 26), with the flange 2), the gasket 3) and the screws 4)
supplied with the burner.
See the accompanying instructions for the adjustment of the gas
train.
5.9.4
Gas pressure
Tab. O indicates the pressure drop of the combustion head and
the gas butterfly valve depending on the operating output of the
burner.
Tab. O
The values shown in Tab. O refer to:
–
Natural gas G 20 NCV 9.45 kWh/Sm
3
(8.2 Mcal/Sm
3
)
–
Natural gas G 25 NCV 8.13 kWh/Sm
3
(7.0 Mcal/Sm
3
)
Column 1
Load loss at combustion head.
Gas pressure measured at the test point 1)(Fig. 27), with:
•
combustion chamber at 0 mbar;
•
burner working at maximum output;
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 27) with maximum
opening: 90°.
To know the approximate output at which the burner is operating
at its maximum:
–
Subtract the combustion chamber pressure from the gas
pressure measured at test point 1)(Fig. 27).
–
Find, in the Tab. O relating to the burner concerned, column
1, the pressure value closest to the result you want.
–
Read the corresponding output on the left.
Example with natural gas G 20:
Maximum output operation
Gas pressure at test point 1)(Fig. 27)
=
16.0 mbar
Pressure in combustion chamber
=
3.0 mbar
16.0 - 3.0
=
13.0 mbar
A maximum output of 1600 kW shown in Tab. O corresponds to
20.3 mbar pressure, column 1.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To know the required gas pressure at test point 1)(Fig. 27), set
the maximum output required from the burner operation, then:
–
find the nearest output value in the Tab. O for the burner in
question.
–
Read, on the right (column 1) the socket pressure 1)(Fig. 27).
–
Add this value to the estimated pressure in the combustion
chamber.
DANGER
Disconnect the electrical power using the main
system switch.
Check that there are no gas leaks.
Beware of train movements: danger of crushing of
limbs.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
The operator must use appropriate tools for instal-
lation.
WARNING
The gas solenoids must be as close as possible to
the burner, to ensure that the gas reaches the
combustion head within the safety time of 3s.
Ensure that the maximum pressure to the burner
is within the calibration range of the pressure reg-
ulator.
Fig. 26
D722
kW
1
p (mbar)
2
p (mbar)
G 20
G 25
G 20
G 25
RS 160
/E O
2
BLU
930
5.6
8.4
0.0
0.0
1100
7.5
11.2
0.0
0.0
1300
9.7
14.5
0.8
1.2
1600
13.0
19.4
3.0
4.5
1860
17.7
26.4
3.8
5.7
R
S
20
0/E O
2
BLU
1383
9.0
13.4
3.1
4.7
1500
10.7
16.0
3.7
5.5
1800
14.7
21.9
5.3
7.9
2100
20.3
30.3
7.2
10.7
2400
28.0
41.8
9.4
14.0
Содержание RS 160/E O2 BLU
Страница 2: ...Translation of the original instructions...
Страница 44: ...20164541 42 GB Appendix Electrical panel layout 0 1 0 0 1 1 1 1 0 2 0 0 3 3 3 4 3 5 3 3 3 3 3 3 3 3 3 3 4 3...
Страница 45: ...43 20164541 GB Appendix Electrical panel layout...
Страница 46: ...20164541 44 GB Appendix Electrical panel layout 0 0 0 1 2 3 2 3 2 4 2 5 2 2 2 2 2 32 3 2 62 6 6 3 2 2 4 2...
Страница 47: ...45 20164541 GB Appendix Electrical panel layout...
Страница 48: ...20164541 46 GB Appendix Electrical panel layout...
Страница 49: ...47 20164541 GB Appendix Electrical panel layout...
Страница 50: ...20164541 48 GB Appendix Electrical panel layout 0 0 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 51: ...49 20164541 GB Appendix Electrical panel layout 0 1 0 1 0 2 0 3 0 0 0 0 0 10 1 0 40 4 4 1 0 0 2 0 5...
Страница 55: ...53 20164541 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...
Страница 57: ......
Страница 58: ......
Страница 59: ......