Installation
Example with natural gas G 20:
Required burner maximum output operation: 1600 kW
Gas pressure at output of 1600 kW
=
13.0 mbar
Pressure in combustion chamber
=
3.0 mbar
13 + 3.0
=
16.0 mbar
pressure required at test point 1)(Fig. 27).
WARNING
The heat output and gas pressure data in the
head refer to operation with gas butterfly valve
fully open (90°).
Fig. 27
S8716