19
GENERAL INFORMATION
1.5
Air vent
The rooms must be equipped with one or more permanent air vents positioned on external walls, ensuring that the all regulations
established in the country of installation are complied with.
For Italy:
The air vents must not have a surface area less than the minimum value indicated in the table (expressed in cm
2
):
Rooms above the ground
Model
Condexa PRO
35 P
50 P
57 P
70 P
90
100
115
135
No. of
Boilers
MINIMUM DIMENSION OF AIR VENT (cm
2
)
2
3000*
3000*
3000*
3000*
3000*
3000*
3000*
3000*
3
3000*
3000*
3000*
3000*
3000*
3000*
3360*
3930*
4
3000*
3000*
3000*
3000*
3600*
3880*
4480*
5240
5
3000*
3000*
3000*
3400*
4500*
4850*
5600
6550
6
3420*
3420*
3420*
4080*
5400
5820
6720
7860
7
3990*
3990*
3990*
4760*
6300
6790
7840
9170
8
4560*
4560*
4560*
5440
7200
7760
8960
10480
9
5130
5130
5130
6120
8100
8730
10080
ND
10
5700
5700
5700
6800
9000
9700
11200
ND
(*)
5000 cm
2
in the case of G30-G31
Rooms below ground, down to a distance of - 5 m from the reference floor level:
Model
Condexa PRO
35 P
50 P
57 P
70 P
90
100
115
135
No. of
Boilers
MINIMUM DIMENSION OF AIR VENT (cm
2
)
2
3000
3000
3000
3000
3000
3000
3360
3930
3
3000
3000
3000
3060
4050
4365
5040
5895
4
3420
3420
3420
4080
5400
5820
6720
7860
5
4275
4275
4275
5100
6750
7275
8400
9825
6
5130
5130
5130
6120
8100
8730
10080
11790
7
5985
5985
5985
7140
9450
10185
11760
13755
8
6840
6840
6840
8160
10800
11640
13440
15720
9
7695
7695
7695
9180
12150
13095
15120
ND
10
8550
8550
8550
10200
13500
14550
16800
ND
Rooms below ground, at a distance of between - 5 m and - 10 m below the reference floor level (with a minimum of 5000 cm
2
):
Model
Condexa PRO
35 P
50 P
57 P
70 P
90
100
115
135
No. of
Boilers
MINIMUM DIMENSION OF AIR VENT (cm
2
)
2
5000
5000
5000
5000
5000
5000
5000
5240
3
5000
5000
5000
5000
5400
5820
6720
7860
4
5000
5000
5000
5440
7200
7760
8960
10480
5
5700
5700
5700
6800
9000
9700
11200
13100
6
6840
6840
6840
8160
10800
11640
13440
15720
7
7980
7980
7980
9520
12600
13580
15680
18340
8
9120
9120
9120
10880
14400
15520
17920
20960
9
10260
10260
10260
12240
16200
17460
20160
ND
10
11400
11400
11400
13600
18000
19400
22400
ND
0
It is not permitted to install systems for relative gas density greater than 0.8 (G30-G31) in rooms with flooring below the natural
ground level.
9
The aeration surface area must not in any case be less than 3000 cm
2
or 5000 cm
2
if using gas with a density exceeding 0.8
(G30-G31).
9
The air vents in rooms with appliances supplied with gas must meet all fire prevention requirements, in particular Ministerial
Decree of 12th April 2011 and subsequent updates.
Содержание Condexa PRO 100
Страница 32: ...32 INSTALLATION 7 Position the GAS manifold 8 Secure the GAS manifold to the frame 7 7 8...
Страница 33: ...33 INSTALLATION 9 Position the manifold closing plugs from the required side 9 22mm 51mm...
Страница 36: ...36 INSTALLATION 7 Position the GAS manifold 8 Secure the GAS manifold to the frame 8 8 7...
Страница 37: ...37 INSTALLATION 9 Position the manifold closing plugs from the required side 9 22mm 51mm...
Страница 83: ...83 COMMISSIONING AND MAINTENANCE...