77
COMMISSIONING AND MAINTENANCE
6.3.1
Parameters specific to cascade systems
Parameters are listed base on the reference menu.
Reference Menu
M1
Parameters Menu
M2
Cascaded module configuration menu
M3
Cascaded boiler configuration menu
M4
Appliance configuration menu
Access type
U
End user
I
Installer
O
Manufacturer
Menu Par.
No.
Nr. dis-
played
Display
Description
Range
Factory
setting
UM
Access
type
Category
M2
72
Permit
Emergency
Mode
Activates the emergency mode. This mode
comes on when communication between
Managing and the primary circuit's probe
is lost. In this event, if Par. 72 is set to
"Yes", the cascade is initiated, working to
the fixed set-point determined by Par. 74.
Yes/No
Yes
U
Cascade
M2
74
Emergency
Set-point
Set-point active in emergency mode.
20…65
70
°C
I
Cascade
M2
75
Delay
Per Start
Next
Mod.
Defines the stand-by time in seconds to
restart the subsequent cascade module in
normal start mode.
5…255
120
Sec.
I
Cascade
M2
76
Delay
Per Stop
Next
Mod.
Defines the stand-by time in seconds to
switch off the last cascade module on in
normal Off mode.
5…255
30
Sec.
I
Cascade
M2
142
Delay
Quick
Start
Next
Defines the stand-by time in seconds to
restart the next cascade module in quick
start mode.
5…255
60
Sec.
I
Cascade
M2
143
Delay
Quick
Stop
Next
Defines the stand-by time in seconds to
switch off the last cascade module on in
Quick Stop mode.
5…255
15
Sec.
I
Cascade
M2
77
Hyst.
Down
Start
Module
Defines by how many degrees the tem-
perature measured by the primary circuit's
probe must fall below the set-point in
order for the subsequent module to be
started after the time interval set by Par.
75.
0…40
5
°C
I
Cascade
M2
78
Hyst.
Up Stop
Module
Defines by how many degrees the tem-
perature measured by the primary circuit's
probe must go above the set-point in
order for the subsequent module to be
switched off after the time interval set by
Par. 76.
0…40
4
°C
I
Cascade
M2
144
Hyst.
Down
Quick
Start
Defines by how many degrees the tem-
perature measured by the primary circuit's
probe must go below the set-point in
order for the subsequent module to be
started after the time interval set by Par.
142 (quick-start mode).
0…40
20
°C
I
Cascade
M2
145
Hyst. Up
Quick
Stop
Defines by how many degrees the tem-
perature measured by the primary circuit's
probe must go above the set-point in
order for the subsequent module to be
switched off after the time interval set by
Par. 143 (quick stop mode).
0…40
6
°C
I
Cascade
M2
146
Hyst. Up
Stop All
Defines by how many degrees the tem-
perature measured by the primary circuit's
probe must go above the set-point in
order for all "On" modules to be switched
off at the same time.
0…40
8
°C
I
Cascade
M2
147
Number
of Units
Defines the number of modules of which
the cascade consists.
1…16
8
I
Cascade
Содержание Condexa PRO 100
Страница 32: ...32 INSTALLATION 7 Position the GAS manifold 8 Secure the GAS manifold to the frame 7 7 8...
Страница 33: ...33 INSTALLATION 9 Position the manifold closing plugs from the required side 9 22mm 51mm...
Страница 36: ...36 INSTALLATION 7 Position the GAS manifold 8 Secure the GAS manifold to the frame 8 8 7...
Страница 37: ...37 INSTALLATION 9 Position the manifold closing plugs from the required side 9 22mm 51mm...
Страница 83: ...83 COMMISSIONING AND MAINTENANCE...