Reset function
In order to reset the boiler’s operation in the event of a
fault, it is necessary to access the fault description screen.
If the lockout is of a non-volatile type that requires a reset
procedure, this will be indicated on the screen, and can be
performed by pressing the
“ok”
button on the REC10CH.
At this point, if the correct operating conditions have been
restored, the boiler will restart automatically.
There are a maximum of 3 consecutive attempts at a release
by the REC10CH
,
should all 3 attempts at reset fail, the
appliance will require to be isolated briefly from the electrical
supply in order to carry out any further reset attempts. Once
the electrical supply has been restored, further attempts
at reset can be carried out. In case of all the attempts are
exhausted the definitive fault E099 occurs on the display.
E020
LIMIT THERMOSTAT
REC10 ATTEMPTS EXHAUSTED
b
If the attempts to reset the boiler are unsuccessful,
please contact the Vokera technical helpline.
For fault E041
If the pressure drops below the safety pressure limit of
0.3 bar the boiler displays the fault code “E041 - WATER
TRANSDUCER LOAD THE SYSTEM” for a transitional time
of 30 sec
during which it is possible to open the external filling
tap until the pressure is between 1 and 1.5 bar.
E041
WATER TRANSDUCER
LOAD THE SYSTEM
b
If the pressure drops frequently, contact your installer or
the Vokera customer care centre.
For fault E060
The boiler is working normally, but does not provide any
stability of the domestic hot water temperature that, in any
event, is supplied at a temperature of around 50°C. The
intervention of an engineer will be required.
For fault E091
The boiler has an auto-diagnostic system which, based on
the total number of hours in certain operating conditions, can
signal the need to clean the primary exchanger (alarm code
E091). Once the cleaning operation has been completed,
reset to zero the total hour meter following the procedure
indicated below:
- select TECHNICAL
EXHAUST PROBE RESET
CONFIRM or CANCEL.
CONFIRM OR DELETE SELECTION
CONFIRM
CANCEL
THE PARAMETER WILL BE
CHANGED
RANGE RATED
CALIBRATION
WEATHER COMPENSATION
COMBUSTION ANALYSIS
EXHAUST PROBE RESET
INSTALLER
TECHNICAL
NOTE:
the meter resetting procedure should be carried out
after each in-depth cleaning of the primary exchanger or if
this latter is replaced.
The total hours can be verified in the following way: INFO
menu
EXHAUST PROBE (see “2.8 INFO” - User
section).
Boiler faults list
ERROR
CODE
ERROR MESSAGE
DESCRIPTION OF
ALARM TYPE
E010
flame lockout/ACF electronic fault
final
E011
extraneous flame
transitional
E020
limit thermostat
final
E030
fan fault
final
E040
water transducer - check system water pressure
final
E041
water transducer - check system water pressure
temporary
E042
water transducer fault
final
E060
domestic hot water probe fault
temporary
E070
fault flow sensor • overtemperature flow sensor • flow/return sensor differential alarm
temporary • final • final
E077
main zone water thermostat
temporary
E080
fault return line probe • return line probe overtemperature • outlet/return line probe differential alarm
temporary • final • final
E090
fault flue gases probe • flue gases overtemperature probe
temporary • final
E091
clean primary heat exchanger
temporary
E099
reset attempts exhausted, boiler blocked
definitive, not resettable
--
water pressure low - verify the system pressure
temporary
--
water pressure high check system
temporary
--
boiler board communication lost
temporary
--
BUS 485 communication lost
temporary