GTR207 Installation Manual:
Rev 1b
23
Dip Switch Adjustment:
Number
Description
Automatic Close Function
1 ON 2 OFF: automatic close delay time is 3s.
1 OFF 2 ON: automatic close delay time is 10s.
1 ON 2 ON: automatic close delay time is 30s.
1 OFF 2 OFF: no automatic close function.
Default position is 1 OFF 2 OFF
Remote Control Mode
leave in OFF position unless an additional module is used.
Default position is OFF
External Button Mode
Leave in OFF position unless an additional module is used.
Default position is OFF
4 OFF: Hard wire keypad
Left/Right Open Setting
OFF – Right hand open
ON – Left hand open
Gate close direction will be changed after motor is restarted
Default position is OFF (right hand)
Spring Limit Switch
Leave in the OFF position,
OFF - Normal close
ON - Normal open
Default position is OFF
Stall Force
ON - Enabled
OFF - Disabled
Default position is ON
Infrared Detection Delay When Closing
ON – Infrared detection delay is set to 1 second
OFF – Infrared detection delay is disabled
Default position is OFF