Setpoints
© Rice Lake Weighing Systems
●
All Rights Reserved
63
%REL
Percent relative setpoint. Performs functions based on a specified percentage of the target value of a
referenced setpoint, using the same weight mode as the referenced setpoint. The actual target value of
the %REL setpoint is calculated as a percentage of the target value of the referenced setpoint.
X
X
RESREL
Relative to a result setpoint. Performs functions based on a specified percentage of the captured value
of a referenced setpoint, using the same weight mode as the referenced setpoint. The actual target
value of the RESREL setpoint is calculated as a percentage of the captured value of the referenced set
-
point, rather than the target value.
X
X
PAUSE
Pauses the batch sequence indefinitely. A BATSTRT signal must be initiated to continue the batch pro
-
cess.
X
DELAY
Delays the batch sequence for a specified time. The length of the delay (in tenths of a second) is spec
-
ified on the VALUE parameter.
X
WAITSS
Wait for standstill. Suspends the batch sequence until the scale is at standstill.
X
COUNTER
Specifies the number of consecutive batch sequences to perform. Counter setpoints should be placed
at the beginning of a batch routine.
X
AUTOJOG
Automatically checks the previous weight-based setpoint to verify the setpoint weight value is satisfied
in a standstill condition. If the previous setpoint is not satisfied when at standstill, the AUTOJOG set
-
point activates the digital output of the previous weight-based setpoint for a period of time, specified on
the VALUE parameter. The autojog process repeats until the previous weight-based setpoint is satisfied
when the scale is at standstill.
NOTE: The AUTOJOG digital output is typically used to signify that an autojog
operation is being performed. AUTOJOG should not be assigned to the same digital
output as the related weight-based setpoint.
X
COZ
Center of zero. Monitors for a gross zero condition. The digital output associated with this setpoint kind
is activated when the referenced scale is a center of zero. No value is required for this setpoint.
X
INMOTON
In motion. Monitors for an in-motion condition. The digital output associated with this setpoint is acti
-
vated when the scale is not at standstill. No value is required for this setpoint.
X
INRANGE
In range. Monitors for an in-range condition. The digital output associated with this setpoint is activated
when the scale is within capacity range. No value is required for this setpoint.
X
BATCHPR
Batch processing signal. The digital output associated with this setpoint is activated whenever a batch
sequence is in progress. No value is required for this setpoint.
X
TIMER
Tracks the progress of a batch sequence based on a timer.
The timer value, specified in tenths of a second on the VALUE parameter, determines the length of time
allowed between start and end setpoints. The indicator START and END parameters are used to spec
-
ify the start and end setpoints. If the END setpoint is not reached before the timer expires, the digital
output associated with this setpoint is activated.
X
CONCUR
Allows a digital output to remain active over a specified portion of the batch sequence. Two types of
concur setpoints can be configured:
Type 1 (VALUE=0)
:
The digital output associated with this setpoint becomes active when the START
setpoint becomes the current batch step and remains active until the END setpoint becomes the current
batch step.
Type 2 (VALUE > 0)
:
If a non-zero value is specified for the VALUE parameter, that value represents
the timer, in tenths of a second, for this setpoint. The digital output associated with this setpoint
becomes active when the START setpoint becomes the current batch step and remains active until the
timer expires.
X
DIGIN
Digital input setpoint. Requires a specific group of digital inputs to be in low (0 VDC) state to satisfy the
setpoint. The digital output associated with this setpoint is held in a low (0 VDC) state until the inputs
selected for the digital input mask are all in a low state.
X
X
AVG
Average setpoint. Performs functions based on the calculated average weight over a specified number
of A/D samples.
NOTE: This setpoint is based on the
raw
A/D weight value, rather than the rounded
value shown on the indicator display. For example, if the display shows 50.0 but the
actual raw A/D value is 49.99, the setpoint will not be satisfied.
X
Kind
Description
Batch
Continuous
Table 8-1. Setpoint Kinds (Continued)