Configuration
© Rice Lake Weighing Systems
●
All Rights Reserved
37
SOFTKEYS
<blank>
Time/Date
Display Tare
Display Accum
Display ROC
Setpoint
Batch Start
Batch Stop
Batch Pause
Batch Reset
Weigh In
Weigh Out
Truck Regs
Unit ID
Select Scale
Diagnostics
Alibi
F1–F10
Use the
Add
and
Remove
softkeys to select softkeys to be displayed in weighing mode.
KYBDLK
OFF
ON
Keyboard lock. Specify ON to disable the keypad in normal mode.
ZERONLY
OFF
ON
Zero key only. Specify ON to disable all front panel keys except ZERO in normal mode.
PROMPTS
PROMPT1–
PROMPT60
Specify prompts for use in setpoint names. Prompts are referenced by the NAME parameter under the
SETPTS submenus; prompts can be shown on the display during setpoint execution.
REGULAT
NTEP
CANADA
INDUST
NONE
OIML
Regulatory mode. Specifies the regulatory agency having jurisdiction over the scale site.
OIML, NTEP, and CANADA modes allow a tare to be acquired at any weight greater than zero. NONE
allows tares to be acquired at any weight value.
OIML, NTEP, and CANADA modes allow a tare to be cleared only if the gross weight is at no load. NONE
allows tares to be cleared at any weight value.
NTEP and OIML modes allow a new tare to be acquired even if a tare is already present. In CANADA mode,
the previous tare must be cleared before a new tare can be acquired.
NONE, NTEP and CANADA modes allow the scale to be zeroed in either gross or net mode as long as the
current weight is within the specified ZRANGE. In OIML mode, the scale must be in gross mode before it
can be zeroed; pressing the ZERO key in net mode clears the tare.
INDUST provides a set of subparameters to allow customization of tare, clear, and print functions in non-
legal-for-trade scale installations. See Level 4 parameter descriptions in Table 3-9.
The value specified for this parameter affects the function of the front panel TARE and ZERO keys. See
for a complete description of TARE and ZERO key functions for each of the regula
-
tory modes.
REGWORD
GROSS
BRUTTO
Sets the term displayed when weighing in gross mode. Selecting BRUTTO replaces the
Gross
annuncia
-
tor with
Brutto
.
CONTACT
—
Allows specification of contact information for use in
iQUBE
alert messages. See Level 3 submenu descrip
-
tions in Table 3-8.
LOCALE
OFF
ON
Locale. Set this parameter ON to enable the LATUDE and ELEVAT parameters. Specifying latitude and ele
-
vation of the scale site provides compensation for gravitational effects. Attached scales must be recalibrated
after changing this parameter from OFF to ON.
NOTE:
Gravitational compensation settings do not affect iQUBE scales.
LATUDE
45
0–90
Latitude. Specify the latitude of the scale site in degrees. This parameter is shown only if LOCALE=ON.
ELEVAT
345
±0–9999
Elevation. Specify the elevation of the scale site in meters. Valid values are –9999 through 9999. This
parameter is shown only if LOCALE=ON.
FEATURE Menu
Parameter
Choices
Description
Table 3-7. FEATURE Menu Parameters (Continued)