3.10 SETTING PORT CONFIGURATIONS
Each of the RFL 9660's device ports must be set to match the interface requirements of the device connected to
it. During installation (Section 2), you listed these devices in the table in Section 12, next to the port to which
they are connected. If you have not finished filling in this table, do it now. You will need this information during
the following procedures. (Refer to the manufacturer's documentation for the device connected to each port or
the application notes in Section 15 of this manual for the information you will need to complete the table in
Section 12.)
3.10.1 ENTERING THE PORT CONFIGURATION MODE
To set port configuration, you most enter the port configuration mode.
To do this, you must be logged on to
the RFL 9660 as a super-user, with the "LOCAL>" prompt on your terminal.
If the "CONFIG>" prompt is
shown, you are still in the switch configuration mode; press the
[Q]
key to return to the "LOCAL>" prompt.
1. Press
the
[P]
and
[ENTER]
keys.
The RFL 9660 will send the following prompt to your terminal:
LOCAL> Port # _
2.
Enter the number of the port to be programmed, and then press the
[ENTER]
key.
If you enter a number that is greater than the number of ports the RFL 9660 has, the following error
message will appear:
Cannot select port > than (maximum number of ports)
If you enter a number between one and the maximum number of ports the RFL 9660 has (8, 16, 24, or
32), a port information display similar to the one shown in Figure 3-8 will appear.
If you have a printer connected to your terminal, it would be helpful to print out this
screen. You would then have a hard copy to refer to during the rest of this procedure.
Port
#
n
(
)
Interface -RS232
Call
Out -Off
Baud
Rate
-2400
Call
Request
-None
Data
Bits -8
Call
Priority
-0
Parity
-None
Call
String
-
Stop
Bits -1
Remote
String
-
Port
Flow
Ctrl
-None
Port
String
-
Local
Port
DTR
-On
Modem
String
-
Local
Flow
Ctrl
-On
Port
Password
-
To change type Y: _
Figure 3-8. Typical port information display, showing factory default values
RFL 9660
RFL Electronics Inc.
October 1, 1999
3-14
(973) 334-3100
Содержание RFL 9660
Страница 39: ......
Страница 132: ...Figure 8 4 Programmable jumpers Direct Digital I O module RFL 9660 RFL Electronics Inc April 24 2007 8 7 973 334 3100 ...
Страница 133: ...This page intentionally left blank RFL 9660 RFL Electronics Inc April 24 2007 8 8 973 334 3100 ...
Страница 149: ...RFL 9660 RFL Electronics Inc August 18 1998 12 2 973 334 3100 ...
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 199: ...RFL 9660 RFL Electronics Inc April 24 2007 14 18 973 334 3100 This page intentionally left blank ...
Страница 206: ...RFL 9660 RFL Electronics Inc April 24 2007 14 26 973 334 3100 This page intentionally left blank ...
Страница 212: ...RFL 9660 RFL Electronics Inc April 24 2007 14 34 973 334 3100 This page intentionally left blank ...
Страница 234: ...RFL 9660 RFL Electronics Inc April 24 2007 14 64 973 334 3100 This page intentionally left blank ...