Figure 9-1. Programmable DIP switches and indicators, fiber optic master I/O module
DATA
The DATA indicator lights when the fiber optic loop is running and the data being sent
is
valid.
ACTIVE
The ACTIVE indicator lights whenever a fiber optic port is being accessed.
RX
The incoming fiber optic cable is connected to the RX connector.
TX
The outgoing fiber optic cable is connected to the TX connector.
S1
TX PWR switch S1 controls the master I/O module's optical output power:
Output
S1-1
S1-2
-42 dBm
OFF (up)
OFF (up)
-38 dBm
ON (down)
OFF (up)
-34 dBm
OFF (up)
ON (down)
-33 dBm
ON (down)
ON (down)
NOTE
These are typical power output levels when jumper J5 is in position ‘A’ (run mode), on Fiber Optic Master I/O
Module (Assembly No. 104430) as shown in the schematic of Figure 14-23 on page 14-55. Position ‘B’ (test
mode) is for factory use only.
RFL 9660
RFL Electronics Inc.
April 24, 2007
9-2
(973) 334-3100
Содержание RFL 9660
Страница 39: ......
Страница 132: ...Figure 8 4 Programmable jumpers Direct Digital I O module RFL 9660 RFL Electronics Inc April 24 2007 8 7 973 334 3100 ...
Страница 133: ...This page intentionally left blank RFL 9660 RFL Electronics Inc April 24 2007 8 8 973 334 3100 ...
Страница 149: ...RFL 9660 RFL Electronics Inc August 18 1998 12 2 973 334 3100 ...
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 199: ...RFL 9660 RFL Electronics Inc April 24 2007 14 18 973 334 3100 This page intentionally left blank ...
Страница 206: ...RFL 9660 RFL Electronics Inc April 24 2007 14 26 973 334 3100 This page intentionally left blank ...
Страница 212: ...RFL 9660 RFL Electronics Inc April 24 2007 14 34 973 334 3100 This page intentionally left blank ...
Страница 234: ...RFL 9660 RFL Electronics Inc April 24 2007 14 64 973 334 3100 This page intentionally left blank ...