Only enable a single device at a time for processing messages with the
self-address destination so that multiple devices do not respond. The
function is disabled by default.
Use Double Output Trip/Close:
this feature is used by a Control Relay
Output Block (CROB) command. When sending Trip/Close control
codes, this configuration controls which Binary Output will receive the
pulse command. If the configuration is disabling (default), both the Trip
and the Close controls will be directed to the point number specified in
the CROB request. If the configuration is enabled, then a CROB
command containing a Close control code will be redirected to the
next highest Binary Output channel.
Site ID:
the field is a user-assigned string that can be read by the DNP3
master station as part of the Device Attributes, Group 0 Variation 246
object.
Location Name:
the field is a user-assigned string that can be read by
the DNP3 master station as part of the Device Attributes, Group 0
Variation 245 object.
Outstation Name:
the field is a user-assigned string that can be read by
the DNP3 master station as part of the Device Attributes, Group 0
Variation 247 object.
Serial Number:
the field is a user-assigned string that can be read by the
DNP3 master station as part of the Device Attributes, Group 0 Variation
248 object. It is recommended that user uses actual device serial
number or IMEI for the setting.