Point Number:
the field specifies the DNP3 identifier for each binary
Output channel. The valid range is 0-65535. The Point Number must be
unique for each Binary Input Channel. Note that the same Point
Number can also be used by a Binary Input Channel.
Static Variation:
the field defines the data object returned in response
to a DNP3 static data poll request (e.g. Class 0 request). This attribute
must be defined for each binary output point. The following table lists
the valid types for Binary Input point types:
Static Object Type
Group Variation Description
g10v2 Binary
Output Status
10
2
Binary Output with Status
Information
Data Class:
the Data Class attribute affects the way the data is reported
externally from the Universal Hub. If a point configuration has a point
Data Class other than Local, changes will be reported to the SCADA
master in the indicated DNP3 data class.
If a point configuration has a point Data Class of Local, it is not available
to the SCADA master through the Class 0 mechanism. Points configured
as Local are accessible via a DNP3 "Level 3" read request.
Valid point Data Class values are Local and Class 0.
Clear Outputs on Comms Inactivity:
The field defines a time in seconds
of no DNP3 comms activity before all binary outputs are driven to the
“OFF” state. This allows for outputs to be put into an assumed “safe”