background image

Form RGM 433-CV/LN, Mfg No. 177854 (Revision 1), Page 11

12. Gas Piping and Pressures

WARNING: This appliance is equipped for a
maximum gas supply pressure of 1/2 pound, 8 ounces,
or 14 inches water column. Supply pressure higher
than 1/2 pound requires installation of an additional
lockup-type service regulator external to the unit.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve
from the gas supply line which is to be tested. Cap or plug the supply
line.

Test Pressures Below 1/2 PSI: Before testing, close the manual valve
on the heater.

All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI/Z223.1a (latest edition), published by
the American Gas Association or CAN/CGA-B149.1 and B149.2, pub-
lished by the Canadian Gas Association (See Paragraph 1). Gas supply
piping installation should conform with good practice and with local

Figure 6 - Supply
Piping Connection

n

 

Vent System Joints

Follow the pipe manufacturer's instructions for joining Type B
double-wall vent pipe sections.

For joining double-wall pipe to the heater outlet collar or single-
wall pipe, follow the "boxed" instructions below:

Instructions for attaching double-wall (Type B) vent pipe to the
heater outlet or single-wall pipe run

Hardware and Sealant Required: 3/4" long sheetmetal screws; and a
tube of silicone sealant

1) Look for the "flow" arrow on the vent pipe; attach according to
the arrow. Slide the pipe so that the heater outlet or the single-wall
pipe is inside the double-wall pipe.

2) Drill a hole through the pipe into the outlet collar or the single-
wall pipe. (Hole should be slightly smaller than the sheet metal
screw being used.) Using a 3/4" long sheet metal screw, attach the
pipe. Do not overtighten. Repeat, drilling and inserting two addi-
tional screws evenly spaced (120

o

 apart) around the pipe.

3) Use silicone sealant to seal any gaps. If there is an annular open-
ing, run a large bead of sealant in the opening. The bead of sealant
must be large enough to seal the opening, but it is not necessary to
fill the full volume of the annular area.

If using single-wall, 26-gauge or heavier galvanized pipe in the
vent connector of an appliance, secure slip-fit connections using
sheet metal screws or rivets. Seal pipe joints with high-temperature
tape or sealant. NOTE: The Model FT requires double-wall vent
connector pipe.

When attaching a vent connector to a masonry chimney, use a thimble
or slip joint to facilitate removal. Fasten vent connector securely
being sure that it does not extend into the chimney.

n

 

Vent System Support

Lateral runs should be supported every six feet using a non-combus-
tible material, such as strap steel or chain. Do not rely on the heater for
support of either horizontal or vertical vent pipe.

n

 

Vent Terminal

The vent terminal should be a minimum of six feet from adjoining
buildings. The vent terminal should be six inches higher than the an-
ticipated snow depth but no less than two feet above the roof. Where
the vent extends through the roof, a clearance thimble is required when
the flue pipe extends through combustible materials; follow the re-
quirements of the double-wall pipe manufacturer.

If using a Type B double-wall vent, terminate with a vent cap that meets
the requirements of the double-wall pipe manufacturer..

codes. Support gas piping with pipe hangers, metal strapping, or other
suitable material; do no rely on the heater to support the gas pipe.

Unit heaters are orificed for operation with natural gas having a heat-
ing value of 1000 (± 50) BTUH per cubic ft or propane gas with a
heating value of 2550 BTUH per cubic ft. If the gas at the installation
does not meet these specifications, consult the factory for proper ori-
ficing.
Pipe joint compounds (pipe dope) shall be resistant to the action of
liquefied petroleum gas or any other chemical constituents of the
gas being supplied.
Install a ground joint union and manual shut-off valve upstream of the
unit control system, as shown in Figure 6. The 1/8" plugged tapping in
the shutoff valve provides connection for a supply line pressure test
gauge. The National Fuel Gas Code requires the installation of a trap
with a minimum 3" drip leg. Local codes may require a minimum drip
leg longer than 3" (typically 6").

Gas supply connection is 1/2". Leak-test all connections by brushing
on a leak-detecting solution.

WARNING: All components of a gas supply
system must be leak tested prior to placing
equipment in service. NEVER TEST FOR
LEAKS WITH AN OPEN FLAME. Failure to
comply could result in personal injury, property
damage or death.

Manifold or Orifice Pressure Settings

Measuring manifold gas pressure cannot be done until the heater is in
operation. It is included in the steps of the "Check-Test-Start" proce-
dure in Paragraph 19. The following warnings and instructions apply.

WARNING: Manifold gas pressure must never exceed
3.5" w.c. for natural gas and 10" w.c. for propane
gas.

For Natural Gas: When the heater leaves the factory, the combination
gas valve is set so that the manifold gas pressure is regulated to 3.5"
w.c. Inlet supply pressure to the valve for natural gas must be a mini-
mum of 5" w.c. or as noted on the rating plate and a maximum of 14"
w.c.

For Propane Gas: When the heater leaves the factory, the combina-
tion gas valve is set so that the manifold gas pressure is regulated to
10" w.c. Inlet supply pressure to the valve for propane gas must be a
minimum of 11" w.c. and a maximum of 14" w.c.

Before attempting to measure or adjust manifold gas pressure, the inlet
supply pressure must be within the specified range both when the heater

Содержание FT30-CV

Страница 1: ...ath Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment HAZARD INTENSITY LEVELS 1 DANGER Failure to comply will result in severe perso...

Страница 2: ...and movable scaffold ing In addition the heaters must be located so as to be accessible for servicing adjustment etc 2 Warranty Refer to the limited warranty information on the Warranty Card in the O...

Страница 3: ...and 45 inches mm Top 1 25 Flue Connector 6 152 Access Panel 18 457 Non Access Side 1 25 Bottom 1 25 Rear 18 457 Units must be installed so that the clearances in the table are provided for combustion...

Страница 4: ...ll the assem bly so that the louvers will direct the air downward with the heater in its new position 3 Turn the access panel so that the labels are in an upright position Re attach the panel 10 Suspe...

Страница 5: ...n venting Common Venting Terms and Requirements Common vents must be vertical The common vertical portion may be either a Type B double wall vent a masonry chimney lined with a Type B or listed liner...

Страница 6: ...horizontal length is 6 ft 1 8M Vent Connector of another Category I appliance H R1 R2 Category I Appliance water heater Model FT CV or LN Model FT CV or LN Maximum Length of the Vent Connector of Oth...

Страница 7: ...103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257...

Страница 8: ...8 257 299 203 320 398 265 391 511 339 528 637 413 1 N A N A 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 N A N A 34 83 94 62 121 150 97 185 230 138 246 314 189...

Страница 9: ...776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 9...

Страница 10: ...N A N A 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1090 466 610 1386 597 1 N A N A 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1181 444 560 1537 580 2 N A N A...

Страница 11: ...in Do not rely on the heater for support of either horizontal or vertical vent pipe n Vent Terminal The vent terminal should be a minimum of six feet from adjoining buildings The vent terminal should...

Страница 12: ...40 24 84 51 160 98 320 195 490 299 930 567 100 38 23 79 48 150 92 305 186 460 281 870 531 125 34 21 72 44 130 79 275 168 410 250 780 476 150 31 19 64 39 120 73 250 153 380 232 710 433 175 28 17 59 36...

Страница 13: ...fan motor remains energized for an additional 180 seconds NOTE This is a three trial system should the unit not sense burner flame the unit will lockout for one hour before initiating another trial f...

Страница 14: ...CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS ARE FI...

Страница 15: ...r natural or propane gas The burners are lightweight and factory mounted in an assembly which permits them to be removed as a unit for inspection or service vice technician to inspect the appliance an...

Страница 16: ...r as practical close all building doors and windows and all doors between the space where the heater is and other spaces of the building Turn on clothes dryers and exhaust fans such as range hoods and...

Страница 17: ...urner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a fire explo sion hazard To prevent fuel gas spillin...

Страница 18: ...a year Inspection should in clude all joints seams and the vent cap Replace any defective parts Flame Sensor Refer to Figure 10 and locate the flame sensor Dis connect the wire remove the screw and th...

Страница 19: ...control at the thermostat or main power 6 Faulty combustion air proving switch 6 Replace combustion air proving switch 7 Main valve not operating 7 a Defective valve a If 24 volt is measured at the v...

Страница 20: ..._______________________________________________________ __________________________________________________________________ __________________________________________________________________ Phone ____...

Отзывы: